Settings
7.4.2
Settings for communication
Protocol
Select protocol for main unit via serial communication (RS485).
Note
1) When the protocol is changed, the device number, transmission speed (Baud rate), transmission
format, stop bit and response time will be initialised.
Press <ITEM/∆>, <SHIFT/∇> to select the protocol.
[Set list] MEWT(MEWTOCOL), MODr (MODBUS(RTU)), 645(DL/T645-2007) (initial: MEWT)
Device number
Set an individual device number for each unit when two or more units are connected for serial
communication via RS485.
1435710000/01/05.13
PROT
NO
Press <ITEM/∆>, <SHIFT/∇> to make the setting.
The setting range differs depending on the protocol.
[Set range]
MEWTOCOL:
MODBUS(RTU):
DL/T645-2007:
Increase
Decrease
1 to 99
1 to 247
0 to 9999
(initial:1)
33