6.11.4 Control of twin-head pumps

Twin-head pumps have a GENI module incorporated
in each terminal box. The modules are internally con-
nected via a wire.
The twin-head pumps are factory-set to the control
mode AUTO and the operating mode "alternating op-
eration", which is described below.
The pump has the following operating modes:
• Alternating operation. Pump operation alter-
nates every 24 hours. If the duty pump stops due
to a fault, the other pump will start.
• Standby operation. One pump is operating con-
tinuously. In order to prevent seizing-up, the other
pump will start at a fixed frequency. If the duty
pump stops due to a fault, the other pump will
start.
The operating mode is selected by means of a me-
chanical contact in each module. The contacts in the
two modules must be set to the same position. If the
contacts are positioned differently, "standby opera-
tion" is selected.
Fig. 18
Operating the pump:
Twin-head pumps can be set and operated in the
same way as single-head pumps. The duty pump
uses its setpoint setting, whether it is made by
means of the control panel, via the R100 or via bus.
Note: Both pumps should be set to the same set-
point and control mode. Different settings will result
in different operation when changing between the
two pumps.

6.12 LON module

The LON module offers the possibility of connecting
the pump to a LonWorks network. The module is
used for data transmission between a network and
pumps of the type MAGNA UPE 32-120, 40-120,
50-60 and 65-60.
For further information, see the documentation files
on the floppy disk supplied with the LON module.
6.12.1 Connection to network
Pumps fitted with a LON module are registered by
the LonWorks network in one of the following ways:
• Activate the "Service PIN" button on the module.
Then the module transmits a unique 48 bit
ID-code (Neuron ID), which is registered by the
network.
• The bar code on the module or the additional label
Fig. 19

7. Setting the pump

For the setting of the pump, use:
• control panel.
• R100 remote control.
• bus communication (not described in detail in
Alternating
The following table shows the application of the indi-
operation
vidual operating units and in which section the func-
tion has been described.
Possible settings
Standby operation
AUTO
Automatic night-time duty
Proportional-pressure
control
Constant-pressure control
Setpoint setting
Max. curve duty
Min. curve duty
Constant-curve duty
Temperature influence
Activation/deactivation of
pump buttons
Allocation of pump number
Start/stop
Resetting of fault indica-
tions
Reading of various data
"–" = not available with this operating unit.

7.1 Factory setting

The pump is factory-set to AUTO without automatic
night-time duty.
supplied is scanned and registered by the net-
work. The bar code is in Code 128 format. The ad-
ditional label can be attached to the building in-
stallation plan.
these instructions. Contact GRUNDFOS).
Service PIN
7.2.1
7.7.1
7.2.1
7.7.2
7.2.1
7.7.1
7.2.1
7.7.1
7.2.2
7.5.1
7.2.3
7.5.2
7.2.4
7.5.2
7.5.2
7.7.3
7.7.4
7.7.5
7.2.5
7.5.2
7.2.6
7.5.3
7.6.1 -
7.6.7
15

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis