7.12 GENI module

The GENI module offers the following functions:
External analog 0-10 V control
External forced control
Bus communication via GENIbus

Control of twin-head pumps.

7.12.1 Control of twin-head pumps
Twin-head pumps have a GENI module incorporated
in each control box. The modules are internally
connected via a wire.
Slave
Flow direction
Fig. 17 Master/slave pumps
For connection of the communication cable between
the GENI modules, see pages 345 and 346.
Twin-head pumps are factory-set to the control mode
AUTO
and the operating mode "alternating
ADAPT
operation", which is described below.
Operating modes:
Alternating operation
Pump operation alternates every 24 hours. If the
duty pump stops due to a fault, the other pump
will start.
Standby operation
One pump is operating continuously. In order to
prevent seizing-up, the other pump will start at a
fixed frequency and run for a short period. If the
duty pump stops due to a fault, the other pump
will start.
In air-conditioning systems, standby
operation is recommended to minimise
Note
condensation inside the pump.
7.12.2 Selection of operating mode
Select the operating mode by means of the
mechanical contact in each module.
Operating
Alternating
Standby
Standby
Standby
Master
Fig. 18 Mechanical contact
Operating the pump
Twin-head pumps can be set and operated in the
same way as single-head pumps. The duty pump
uses its setpoint setting, whether it is made on the
control panel, with the R100 or via bus.
Note

7.13 LON module

The LON module offers the possibility of connecting
the pump to a LonWorks network. The module is
used for data transmission between a network and
pumps of the type MAGNA 32-120, 40-120, 50-120,
65-120, 50-60 and 65-60.
For further information, see the documentation files
on the floppy disk supplied with the LON module.
Left pump
mode
head
Alternating
Alternating
Standby
Standby
Both pumps should be set to the same
setpoint and control mode. Different
settings will result in different
operation when changing between the
two pumps.
Right pump
head
Alternating
Standby
Alternating
Standby
Alternating
operation
Standby operation
19