Control card protection:
– External fuse for 24 V DC supply voltage of control terminal X107.
– Rated 4 A DC fuse UL248−14.
– Functional Safety is evaluated according to standards listed in section
"Safety engineering".
The device is provided with internal overload protection. For information on
the protection level of the internal overload protection for a motor load, see
the corresponding Software Manual or Online Help under the topic "Motor
2
load monitoring (I
xt)". This function has to be activated; i. e. the reaction
must be changed from "Warning" (factory setting) to "Fault".
For information on rating and proper connection of the thermal protector
(only for connection to motors having integral thermal protection), see the
corresponding Manual or Online Help.
The device shall be installed in a pollution degree 2 macro−environment.
Maximum surrounding air temperature: 55 °C.
Use 75 °C copper wire only, except for control circuits.
Safety card protection:
– External fuse for 24 V DC supply voltage of control terminal X80.
– Rated 4 A DC fuse UL248−14.
– Functional Safety is not evaluated by UL.
l
Elektrische Installation
Wichtige Hinweise