RS 485 digital interface (RS option)

The RS 485 interface operates with differential levels that are not susceptible to
interference. In this way, cable lengths of up to 1000 m long can be implemented. The
instruments are connected via a 2-wire line. A twisted 3-wire line is recommended for
greater lengths or a larger number of instruments; the third line is used as a reference
potential (GND), to compensate for any possible differences in potential that may
occur.
Terminate every bus with a resistor using the software (see Parameterizing).
The last device on the bus must provide the terminating resistor, i.e. in
parameterization menu item
connected additionally within the bus connection (
notr
disconnected (
If only one device is used, this is also effectively the last device and the terminating
resistor must be connected (
All other technical data as well as operating instructions are given in RS 485
Operating Manual .
USA and Canada:
Use the MCB 17x conduit box for the power supply and relay/alarm
contacts. Follow the installation instructions.
Installation
PIF
, the last device must have the termination
= no Termination) in all other devices.
tr
).
tr
T
=
ermination) and