NiCrSi-NiSi „N"
DIN EN 60584
Pt10Rh-Pt „S"
DIN EN 60584
Pt13Rh-Pt „R"
DIN EN 60584
Pt30Rh-Pt6Rh „B"DIN EN 60584
W3Re-W25Re „D"
Cold junction
Cold junction accuracy
Measuring range
Input filter
Particularities
1.The accuracy values refer to the maximum measuring range.

Direct current

Measuring range
0 ... 20mA, voltage drop < 2V
4 ... 20mA, voltage drop < 2V
0 ... 10V, input resistance > 100 k
2 ... 10V, input resistance > 100 k
Scaling
Measuring range
Input filter
V1.00/EN
-100 ... +1300°C
0 ... +1768°C
0 ... +1768°C
300 ... 1820°C
0 ... 2495°C
Pt 100 internal
± 1K
210 ms, 420ms with double thermocouples (C112=1)
digital filter, 2st priority; filter constant can be set from 0 ... 100s
can also be programmed in °F
Accuracy
0.2%
0.1%
can be freely programmed within the limits
210 ms
digital filter, 2st priority; filter constant can be set from 0 ... 100s
0.4%
0.4%
0.4%
0.4%
0.4%
8 Technical Data
37