V1.00/EN
8.7
Test voltages as per EN 60730, part 1
Input and output against voltage supply
- at a voltage supply AC 110 ... 240V +10% /-15%
- at a voltage supply AC/DC 20 ... 30V, 48...63 Hz
8.8
Electrical safety
Mains to electronic components and probe
Mains to the relay
Relay to electronic components and probe
Relay to Relay
Electrical safety
Protection type I
3.7kV/50Hz
3.7kV/50Hz
Clearances and creep paths
6 mm
8 mm
6 mm
8 mm
6 mm
8 mm
6 mm
8 mm
according to DIN EN 14597 (DIN EN 60730-2-9)
Overvoltage category III, pollution degree 2
with internal separation to SELV current circuits
8 Technical Data
40