V1.00/EN
8
Technical Data
8.1
Analog inputs
RTD temperature probe
Designation
Pt 100
DIN EN 60751
KTY11-6
PTC
Pt 1000
DIN EN 60751
Connection type
Measuring range
Input filter
Particularities
Thermocouples
Designation
Fe-CuNi „L"
DIN 43710
Fe-CuNi „J"
DIN EN 60584
Cu-CuNi „U"
DIN 43710
Cu-CuNi „T"
DIN EN 60584
NiCr-Ni „K"
DIN EN 60584
Measuring range
-200 ... +850°C
-50 ... +150 °C
-200 ... +850°C
2-wire, 3-wire circuit
210 ms
digital filter, 2st priority; filter constant can be set from 0 ... 100s
2xPt100 for differential value calculation, display can also be programmed in °F
Measuring range
-200 ... +900°C
-200 ... +1200°C
-200 ... +600°C
-200 ... +400°C
-200 ... +1372°C
8 Technical Data
1
Accuracy
0.1%
1%
0.1%
1
Accuracy
0.4%
0.4%
0.4%
0.4%
0.4%
36