C112 Setting For Double Thermocouple; C113 Unit, Decimal Places; C114 Device Function - JUMO safetyM TB 08 Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

7.2

C112 Setting for double thermocouple

Only available if C111 is set to 037 ... 048.
v
Chapter 7.1 „C111 Analog inputs"
Double thermocouple
0
no
1
yes
7.3

C113 Unit, decimal places

Unit, decimal places
0
°C, no digit after the decimal point
1
°C, one digit after the decimal
point
2
°F, no digit after the decimal point
3
°F, one digit after the decimal point
7.4

C114 Device function

Device function
0
Initial commissioning/start-up of TB
Temperature limiters
1
Temperature limiter TB
2
Temperature monitor TW
V1.00/EN
Remark
Probe short-circuit is not detected!
Can detect a probe short-circuit
Remark
A
When converting the unit to °F, the measured value is con-
verted. All other values referring to the measured value, e.g.
AL, are maintained !
Remark
The TB remains locked when the mains connection is reactivated indepen-
dent of the switching status of the relay output K1 prior to the mains failure.
Unlocking only required when the temperature is exceeded
automatic unlocking
7 Configuration level