Herunterladen Inhalt Inhalt Diese Seite drucken

Pt100 For Differential Value Calculation As Absolute Value - JUMO safetyM TB 08 Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

V1.00/EN
13.6 2x Pt100 for differential value calculation as absolute value
The change-over to Difference as absolute value is only possible via the setup program.
IN2
Ald = 50°C
300°C
200°C
Hys1
100°C
3
50°C
0°C
-100°C
-200°C
-50°C
-200°C
-100°C
0°C
AL = 150°C (inverse)
13 Setup program
All difference values
Inside the valid
setting for
the difference ALd = 50.
Example 1:
INP = 101°C,
101 - 50 = 51 exceeds Ald = 50 and lies out of the
Example
2:
INP = 50°C, IN2 = 50°C
50 - 50 = 0
and lies inside the valid range
Example
3:
INP = -50°C, IN2 = 50°C
2
-50 - 50 = 100
1
out of the valid range
The area between the dot and dash lines indicate
the span of the hysteresis (factory setting: 1K)
The inputs INP and IN2 are additionally monitored
in regards to the limit value AL=150°C
Hys1
INP
200°C
300°C
100°C
52
diF = INP-IN2 are shown in the picture.
range (green)
all values
are smaller than the
IN2 = 50°C
valid range
.
exceeds
Ald = 50
and lies
.
.

Werbung