JUMO safetyM TB 08 Betriebsanleitung Seite 87

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Switching
behavior
1
Direct
(S-Function)
A
The pre-alarm (UA) is factory-set as an "Absolute value" (C119 = 1) and is responsive to INP and IN2!
If one of the two measured values exceeds the pre-alarm, the KV LED is lit and the KV relay output switches.
V1.00/EN
Remark
If the AL limit value is gone below, the installed relay output K1 switches OFF. The K1 LED is
lit red and the set display value flashes (e.g. INP).
For the temperature limiter, relay output K1 remains in this status even when the measured
value exceeds the limit value AL. Only when the "Reset" key is pressed >3sec or a switch is
activated when the binary input is respectively configured, does the relay output K1 switch on
again and the OK LED is lit green.
The temperature monitor automatically switches the K1 relay output ON and the OK LED is
lit green, when the measured value exceeds the limit value AL.
Relay output KV
active
LED KV lights up yellow
Relay output KV inaktive
LED KV off
Relay K1 aktive
LED OK
lights up
green
5
Relay inaktive
LED K1 lights up red
ALLO
Pre alarm range
Pre alarm
Alarm range
valid range
Ö
P
P
S
3,15A
3,15A
Hys1
6
7
5
AL
Limit Value
7 Configuration level
Hys2
Measured Value
Ö
S
6
7
Measured Value
ALHI
27