FD-1/FD-1N
MONITOR
Then the unit returns to the Display mode and displays the current parameter value
which has just been changed by the parameter abbreviation in the 3-digit alphanu-
meric display.
You can now
• select another parameter and change it or
• exit the Display mode.
When all the parameters have been set and confirmed, return to the Run mode by
pressing the
push-button for approx. 3 s.
When no push-button has been pressed for approx. 15 s, the unit automatically
returns to the Run mode.
Cancel the parameter setting:
If you press the
push-button only briefly when the parameter value has been
changed, or if no push-button is pressed for approx. 15 s, the unit will default back
to its previous settings. The unit returns to the Display mode and indicates the old
parameter value which remains effective.
Locking / Unlocking
The unit can be locked so that unintentional incorrect entries can be avoided:
Press the push-buttons
and
simultaneously and hold them. The "KEY" indica-
tor is flashing.
Release the push-buttons when the indicator is constantly lit in the display.
For unlocking press the push-buttons
and
simultaneously and hold them. The
"KEY" indicator is flashing.
Release the push-buttons when the indicator is no longer displayed.
Test function:
Via this simulation function correct operation of how you have set the units (switch-
ing functions) can be checked before connection to the plant.
Special function wire monitoring (only for FD-1 N)
The monitor FD-1 N continuously monitors the pulse pick-up cable. In case of a wire
break or short circuit transistor outputs (terminal 4 for In1 / terminal 10 for In2) sig-
nal the fault, the respective channel indicator flashes.
With the parameter FWx (see page 16) you can influence the output behaviour in
case of a fault.