Parameterization and configuration

8.10 Preset adjustment function

PNO CLASS 2 16 Bit
TR-Mode High Resolution
● In order that the preset adjustment function can be used in PNO CLASS 2
configurations, the operating parameter "Scaling function" must be
switched on!
● TR-Mode Position/TR-Mode Position+Velocity:
The measuring system can be adjusted to an arbitrary position value in the range 0 to
(measurement length in steps - 1) via the PROFIBUS.
This is achieved by setting the highest value output data bit
31
(2
for PNO CLASS 2-32 bit configurations and the TR-Modes, or 2
CLASS 2-16 bit configuration).
The preset adjustment value sent in the data bytes with the rising flank of the bit
"preset execution" is adopted as the position value.
There is no acknowledgement of the process via the inputs in CLASS 2 mode.
Lower limit
Upper limit
 TR-Electronic GmbH 2004, All Rights Reserved
Page 92 of 115
Risk of injury and damage to property by an actual value jump when the
Preset adjustment function is performed!
 The preset adjustment function should only be performed when the
measuring system is at rest, otherwise the resulting actual value jump must
be permitted in the program and application!
TR-Mode Position
Teach-In function, enabled with status:
Count direction and Preset adjustment can not be executed at the same
29
time. The bits 2
and 2
0
programmed total measuring length in increments – 1
TR - ECE - BA - DGB - 00036 - 10
Availability
PNO CLASS 2 32 Bit
TR-Mode Position+Velocity
TR-Mode High Resolution+Velocity
30
must be set to "0".
Page
85, 86
87, 88
90, 91
15
for the PNO
Printed in the Federal Republic of Germany
10/01/2014