8.11 Description of the operating parameters

8.11.1 Count direction

PNO CLASS 1 16 Bit
PNO CLASS 2 16 Bit
TR-Mode High Resolution
The count direction defines whether ascending position values are output from the
measuring system if the measuring system shaft rotates clockwise or counter-
clockwise (view onto the measuring system flange connection).

8.11.2 Class 2 Functionality

PNO CLASS 2 16 Bit
Defines the functional scope of the measuring system. Class 2 switched off means
only Class 1 functions are active in the measuring system; it does not scale the
position value and is not adjustable.

8.11.3 Commissioning diagnostics

PNO CLASS 2 16 Bit
TR-Mode High Resolution
Defines whether the measuring system triggers a "diagnosis alarm" (OB82 for
SIMATIC
Chapter "Alarms", page 111.
Printed in the Federal Republic of Germany
10/01/2014
TR-Mode Position
TR-Mode Position
S7) for an internal error (memory or value jump > 1 revolution), also see
TR - ECE - BA - DGB - 00036 - 10
Availability
PNO CLASS 1 32 Bit
PNO CLASS 2 32 Bit
TR-Mode Position+Velocity
TR-Mode High Resolution+Velocity
Availability
PNO CLASS 2 32 Bit
Availability
PNO CLASS 2 32 Bit
TR-Mode Position+Velocity
TR-Mode High Resolution+Velocity
Page
84, 84
85, 86
87, 88
90, 91
Page
85, 86
Page
85, 86
87, 88
90, 91