The selection list of the sensor type is displayed depending on the PV unit.
Example: When selecting a resistance thermometer the PV unit must first be
set to .
Sensor 1 has priority, sensor 2 setup is matched to the setup of sensor 1.
Example: Sensor 1 is set up for a 4-wire connection, sensor 2 is set up for a 3-
wire connection; there is an automatic change of sensor 2 to a type K
thermocouple.
Sensor
Input of RTD connection mode.
connection
Input:
• 2-wire
• 3-wire
• 4-wire
Function is only active on selection of a resistance thermometers (RTD) in the
device function SENSOR TYPE (V3H0).
Cold junction
Selection of the internal (Pt100) or an external comparison
measurement point.
Input:
• internal
• external
Function is only active on selection of a thermocouple (TC) in the device
function SENSOR TYPE (V3H0).
External
Input of the external comparison point measurement value.
temperature
Input: -40.0 to 185.0 °F / -40.00 to 85.00 °C (°C, F, K)
32 °F (0 °C)
Function is only active when "external" has been selected in the device
function COLD JUNCTION (V3H2).
2-wire
Input of cable resistance compensation on a 2-wire RTD connection.
compensation
Input: 0.00 to 30.00 
Function is only active when a 2-wire connection has been selected in the
device function SENSOR CONNECTION (V3H1).
Offset
Input of the zero point correction (offset).
Input: -18.00 to 18.00 °F (-10.00 to 10.00 °C)
32.0 °F (0.00 °C)
Measurement
Display of measurement unit.
unit
Sensor 1 unit = PV unit
Serial no.
Input of the serial number of the sensor connected to this sensor input.
sensor
®
Available in ReadWin
2000, HART
Commuwin II with Matrix address
Sensor type
See Function group SENSOR 1
Sensor 1 has priority, sensor 2 setup is matched to the setup of sensor 1.
Example: Sensor 1 is set up for a 4-wire connection, sensor 2 is set up for a
3-wire connection; there is an automatic change of sensor 2 to a type K
thermocouple.
Sensor
See Function group SENSOR 1
connection
Endress+Hauser
Function group SENSOR 1
®
handheld module DXR275/375,
Function group SENSOR 2 (only on a device with 2 sensor inputs)
®
handheld module DXR275/375,
Commissioning
ReadWin
®
2000
DXR275/375,
FieldCare
+
+
+
+
+
+
+
+
+
+
+
+
+
+
®
ReadWin
2000
DXR275/375,
FieldCare
+
+
+
+
CW II-
Matrix
V3H1
V3H2
V3H3
V3H4
V3H5
V3H6
V3H7
CW II-
Matrix
V4H0
V4H1
77