Commissioning
Available in ReadWin
®
2000, HART
Commuwin II with Matrix address
Cold junction
See Function group SENSOR 1
External
See Function group SENSOR 1
temperature
2-wire
See Function group SENSOR 1
compensation
Offset
See Function group SENSOR 1
Measurement
See Function group SENSOR 1
unit
Serial no.
See Function group SENSOR 1
sensor
®
Available in ReadWin
2000, HART
Commuwin II with Matrix address
PV lower
Input of 4 mA value.
range value
Input: Limitation values see device function SENSOR TYPE 1/2.
32 °F (0 °C)
PV upper
Input of 20 mA value.
range value
Input: Limitation values see device function SENSOR TYPE 1/2.
212 °F (100 °C)
Analog output
Input of the standard (4 to 20 mA) or inverse (20 to 4 mA) current output
signal.
Input:
• 4 to 20 mA
• 20 to 4 mA
Filter
Selection of the digital filter 1. order (filter time constant).
Input: 0 to 60 s
HART Output/
Preamble
Multidrop
Device
address
78
Function group SENSOR 2 (only on a device with 2 sensor inputs)
®
handheld module DXR275/375,
Function group OUTPUT
®
handheld module DXR275/375,
Input: Number of response preambles: 0 to 15
5
Input: HART address of the temperature transmitters:
0 to 15
If addresses > 0, the temperature transmitter
is in Multidrop mode and the analog output is set to 4 mA.
Device address is shown on the display in the Multidrop mode
ReadWin
®
2000
DXR275/375,
FieldCare
+
+
+
+
+
+
+
+
+
+
+
+
®
ReadWin
DXR275/375,
2000
FieldCare
+
+
+
+
+
+
+
+
-
+
Endress+Hauser
TMT162
CW II-
Matrix
V4H2
V4H3
V4H4
V4H5
V4H6
V4H7
CW II-
Matrix
V1H4
V1H5
V1H6
V1H7
HART
Server