Carel gaSteam Benutzerhandbuch Seite 65

Inhaltsverzeichnis

Werbung

E516
burner error
only for
UG040
E517
blower error;
E533
water or other material
between the high level
electrodes with no produc.
(conductivity measured
between the electrodes)
E531
high water conductivity
pre-alarm
E521
high ambient humidity
(high temper. in T control)
E522
low ambient humidity
(low temper. in T control)
E524
high outlet humidity
E501
internal memory error
E512
user parameter error
E530
hour counter error
E520
room probe not
properly connected
E523
outlet probe not
properly connected
(if featured)
E525
NTC probe for measuring
the water temperature not
properly connected
(if featured)
E532
routine maintenance signal
E502
activation of the safety
thermostat due to
abnormal overheating of he
boiler following operation
when empty
• burner flame malfunction;
• check the gas pressure and the
phase-neutral connection on the
gaSteam power supply
• switch the machine off, remove
the blower and check
operation
• switch the machine off and check
for leaks from the fill solenoid valve
or deposits of material between
the high level electrodes
• check the conductivity of the
supply water;
• if necessary, install a suitable
water treatment system;
• the problem will not be resolved
by softening the supply water
• check the operation of the probe
and the limit set by parameter P2
• check the operation of the probe
and the limit set by parameter P3
• check the operation of the outlet
probe
• contact the Carel service
department
• with the machine off check that
there are no defective or
malfunctioning electrical
connections
• reset the hour counter (see
Resetting the hour counter)
• check the connection of the
probe and the setting of param.
A0 for ON/OFF configuration
(see Reading and programming
the parameters)
• check the connection of the probe
or the setting of parameter A0
(see Reading and programming
the parameters)
• check the pre-heating operation
and the setting of parameters b1,
b2, b3 (see Reading and
programming the parameters);
• check the connections to the
terminal block on the boiler cover
• stop the machine and carry out
a complete maintenance routine
on the humidifier, resetting the
hour counter (see Resetting
the hour counter)
• stop the machine and carry out a
complete maintenance routine on
the humidifier, resetting the hour
counter (see Resetting the hour
counter)
59
humidifier
manual
disabled
(button 3 in
Fig. 6.3.1)
humidifier
manual
disabled
warning-
auto
warning -
auto
warning -
auto
warning -
auto
warning -
auto
humidifier
Carel
disabled
reprogram.
humidifier
reprogram
disabled
parameters
hour counter
manually
disabled
reset hour
counter
humidifier
auto
disabled
humidity
auto
limiting
disabled
preheating
auto
disabled
warning -
manual
total shut-down power OFF
cod. +030221931 rel. 5.0 - 05.11.2003
active
active
active
not
active
active
active
active
active
active
not active
active
active
active
not active
active