Electrical wiring
Round. Press the terminal
1) The power terminal block should not be crimped with 2 wires of different diameters. Otherwise, poor crimp 
connection will occur and that can lead to abnormal heating or sparking of the line. 
2) Refer to the figure below for crimping wires of same diameter. 
Connect wires with the same
diameter on both the sides
(5) Tighten the terminal screws using the right screw driver. A screw driver of small dimension will damage the
screw head and fail to tighten it properly.
(6)  If  terminal  screws  are  tightened  excessively,  they  could  get  damaged.  Refer  to  the  following  table  for 
tightening torques of terminal screws:
Dimension of terminal screw
M3.5 (terminal block for communication line)
M4 (terminal block for power line)
M4 (terminal block for ground wire)
(7) It is forbidden to connect the power line to the communication terminal block because it will damage the 
circuit control board.
(8) Wiring of the communication lines should be within the following scope. Exceeding the limit will possibly 
lead to abnormal communication:
1) The maximum wiring length between the outdoor machine and the valve cage, the valve cage and the indoor 
machine, and between the valve cages should be 1000 m at most. The total wiring length should be 1000m at 
most.
2) The maximum wiring length between the valve cage and the wire controller for switching working modes 
should be 500 m at the most.
Insulating sleeve
It's forbidden to connect two 
wires on one side
Tightening torque (N.m)
19
Wire
Wires of different diameters 
are not allowed
0.80~0.96
1.18~1.44
1.52~1.86