Electrical wiring
The wiring of the power line and signal line of the connection kit
Cross
Items
Section
Total
(mm
)
2
Current
of Indoor
Units(A)
<10
2
≥10 and <15
3.5
≥15 and <22
5.5
≥22 and <27
10
•   The Power cable and the communication wire should be fixed firmly. 
•   Each connection kit must be earthed well.
•   When the power cable exceeds the dimension range, ensure that you correct it appropriately.
•   Shielded layer of communication wires should be connected together and be earthed at a single point.
•   Communication wire's total length cannot exceed 1000 m.
Graphical representation for wiring
You need to connect the communication terminal block P and Q of the main unit of the outdoor units with the 
communication terminal block P and Q of the first connection kit.
To Power supply
1 PH. 220-230V~
50/60 Hz
Notes:
(1) The above shown wiring example is only for reference. The number of connection kits and indoor units 
shall determine the field installation. 
(2)    Two-core non-polar communication lines with shield shall be used for communication lines between the 
connection kit and the indoor/outdoor unit. 
(3)    All connection kits within one system can share one over-current breaker for power supply.  It is  however  
necessary to compute the total current capacity specification. 
(4) In case of the wiring harness connected to the power terminal block, the terminal is to be pressed using a 
round (refer to the following figure). 
Length
Rated
Rated current of Power
(m)
Current of
Overflow 
Breaker(A)
20
20
20 A,30 mA,0.1S or below
25
30
30 A,30 mA,0.1S or below
30
40
40 A,30 mA,0.1S or below
40
50
50 A,30 mA,0.1S or below
OUTDOOR
Indoor1
Communication wire
with polarity
Wired Controller
leakage breaker (A)
Leaking current (mA) 
operating period (S)
The communication wire of AH devices
and the outdoor unit as well as between 
18
Cross Sectional Area
of Signal Line
outdoor
Connection kit connection 
connection
kit (mm
)
2
2 cores×0.75-2.0mm
shielded line
AH devices with non-polar
Indoor2
Wired Controller
kit (mm
)
2
2
Indoor3
Wired
Controller