Fault: Pump is loud
Possible cause
Pump and pipes not
completely ventilated or
filled.
Suction height too
large/Unit's NPSH
(intake) too low.
Wear of components.
Dynamic head lower than
that indicated in the
order.
Pump strained or
vibrations in the pipes.
Imbalanced rotor.
Pump and/or motor
bearings are damaged.
Flow rate too low.
04/2019
Solution
Ventilate pump.
Fill pump.
Correct the fluid level.
Install pump lower.
Completely open shut-off valve
in the intake.
If the resistance is too large,
modify the intake line.
Check suction basket/suction
opening.
Observe the permitted pressure
reduction speed.
Replace components.
Set operating point exactly.
For constant overload turn the
impeller (further enquiry
required).
Check pipe connections and
pump fasteners, if necessary
reduce the pipe bracket
spacing.
Fasten pipes using vibration
reducing materials.
Clean pump and pump parts.
Replace bearing.
Increase minimum flow rate.
Faults