Factory default settings

Factory default settings
On being started up for the first time, the system operates with the basic factory settings:
– The emergency power supply connection and the alkaline batteries of the central unit are not monitored.
– Mean values are calculated over a period of 30 minutes (for NO
– Alarm threshold settings for the different transmitters:
Actual value Alarm A1
threshold
hysteresis
Actual value Alarm A2
threshold
hysteresis
Actual value Alarm A3
threshold
hysteresis
Actual value Alarm A4
threshold
hysteresis
Mean value Alarm A1
threshold
hysteresis
Mean value Alarm A2
threshold
hysteresis
Mean value Alarm A3
threshold
hysteresis
Mean value Alarm A4
threshold
hysteresis
The transmitter values for other gases are listed in the data sheet of the transmitter concerned.
Hysteresis of e.g. 10 ppm with a limit of e.g. 100 ppm means that the alarm is set at 100 ppm and reset if the
value falls below 90 ppm.
These default settings can only be altered by DrägerService.
58
CO transmitter
NH
transmitter
3
250 ppm
50 ppm
5 ppm
5 ppm
250 ppm
200 ppm
5 ppm
20 ppm
250 ppm
500 ppm
5 ppm
50 ppm
250 ppm
1000 ppm
5 ppm
100 ppm
40 ppm
1200 ppm
4 ppm
0 ppm
80 ppm
1200 ppm
8 ppm
0 ppm
100 ppm
1200 ppm
10 ppm
0 ppm
100 ppm
1200 ppm
10 ppm
0 ppm
15 minutes).
2
O
transmitter
NO transmitter
2
20 % by vol.
10 ppm
0.2 % by vol.
3 ppm
19 % by vol.
15 ppm
0.2 % by vol.
3 ppm
18 % by vol.
20 ppm
0.2 Vol.-%
3 ppm
17 % by vol.
20 ppm
0.2 % by vol.
3 ppm
0 % by vol.
50 ppm
0 % by vol.
5 ppm
0 % by vol.
50 ppm
0 % by vol.
5 ppm
0 % by vol.
50 ppm
0 % by vol.
5 ppm
0 % by vol.
50 ppm
0 % by vol.
5 ppm
NO
transmitter
2
1 ppm
0.1 ppm
2 ppm
0.2 ppm
3 ppm
0.3 ppm
5 ppm
0.5 ppm
1 ppm
0.1 ppm
2 ppm
0.2 ppm
3 ppm
0.3 ppm
5 ppm
0.5 ppm