Wiring diagram
Central unit:
Connection
1 Power (terminal contacts)
230 V, 50 to 60 Hz, max. 300 mA, max. 55 VA
Pin assignment:
[ [ [ [
Caution!
high voltage
2 Terminal board (terminal contacts)
Connection for mains PE and terminals for supplementary installation.
3 Relays (terminal contacts)
The relays are designed as normally closed relays with a potential-free
switching contact.
Potential-free contact – 250 V, 5 A, cos (ϕ) = 1.
Pin assignment K1 to K5:
– Switching contacts shown
in idle state
Recommended use:
Relay 1 set for A1 e.g. for 1st fan stage
Relay 2 set for A2 e.g. for 2nd fan stage
Relay 3 set for A3 e.g. for warning panel
Relay 4 set for A4 e.g. for acoustic warning
Relay 5 set for fault
Examples of pin assignment for power supply and one relay:
– Relay switching contacts supplied with fused supply (L
4 4 A fuse for L
Si
L (Outer conductor, VarioGard power feeder)
L
(Phase conductor output,
Si
with 4 A slow-blow fuse)
N (Neutral conductor)
1
2
➀ ➂
) – max. 4 A.
Si
Installing the VarioGard system
Electrical installation
➀ ➂
L
N
PE
1
2
3
➀ ➂
➀ ➂
➀ ➂
➀ ➂
K1
K2
K3
K4
K5
4
➀ ➂
L
N
PE
➀ ➂
➀ ➂
➀ ➂
➀ ➂
➀ ➂
53