9. Troubleshooting

Problems
Load connected to the generating set during start-up.
Air filter (fig. A – No.14) blocked.
Fuel level too low
Engine does not
Fuel filter (fig. A – No.13) blocked.
start
Oil level too low.
Starter battery (fig. A – No.15) defective.
Fuel supply blocked or leaking.
Fuel level too low
Engine stopped
Oil level too low.
Circuit breakers (fig. A – No. 8) not activated.
Defective devices supply lead
No electric
current
Defective electrical sockets (fig. A - No 9).
Defective alternator.
Device connected or faulty lead.
Triggering the
circuit breakers
Overload (see § Capacity of the generating set).

10. Specifications

Model
Maximum output / Rated output
Acoustic pressure at 1 m
Engine type
Recommended fuel and fuel tank capacity
Recommended oil and oil sump capacity
Oil failure cut-out
Circuit breaker
Direct Current
Alternating Current
Socket types
Spark plug type
Battery
Dimensions L x l x h
Weight (without fuel)
● : Standard

11. Cable sizes

Laying mode = cables on cable tray or racks not perforated / admissible voltage drop = 5% / Multiconductors.
Cable type PVC 70°C (example H07RNF) / Ambient temperature =30°C.
Rated Current (A)
Single-phase
10
16
20
25
32
40
50
63
Probable causes
○ : Option
0 to 50m
mm² / AWG
Three-phase
4 / 10
1.5 / 14
6 / 9
2.5 / 12
10 / 7
2.5 / 12
10 / 7
4 / 10
10 / 7
16 / 5
16 / 5
25 / 3
Disconnect the load.
Clean the air filter (see § Cleaning the air filter).
Fill up with fuel (see § Filling up with fuel).
Replace the fuel filter (see § Replacement of the fuel
filter).
Check
the
(see. § Checking of oil level).
Recharge or replace the starter battery.
Have it checked, repaired or replaced.*
Fill up with fuel (see § Filling up with fuel).
Check
the
(see. § Checking of oil level).
Activate the circuit breakers.
Change the lead
Have it checked, repaired or replaced.*
Have it checked, repaired or replaced.*
Disconnect the device and the lead.
Remove the overload.
* Operation(s) to be entrusted to one of our agents.
Diesel oil
SAE 5W40
2P+T 230V 10/16A
X : Not applicable
Cable lengths
51 to 100m
mm² / AWG
Single-phase
Three-phase
10 / 7
2.5 / 12
10 / 7
4 / 10
16 / 5
4 / 10
16 / 5
6 / 9
25 / 3
35 / 2
35 / 2
50 / 0
Possible solutions
oil
level
and
fill
up
oil
level
and
fill
up
DIESEL 6000 E XL C
5200 W / 4160 W
95 dB(A)
Kohler KD440
1.5 L
X
230V – 18.1A
2P+T 230V 32A
X
81 x 55.5 x 59 cm
103 kg
101 to 150m
mm² / AWG
Single-phase
10 / 7
16 / 5
25 / 3
25 / 3
35 / 2
50 / 0
50 / 0
70 / 2 / 0
if
necessary
if
necessary
16 L
Three-phase
4 / 10
6 / 9
6 / 9
10 / 7