4.4.4 Output Current

Within this option the measuring range can be defined corresponding to the output
current of 4-20 mA.
The beginning of the measuring range might be higher than the end
(inverted signal), eg/ 20 to 180 l/min corresponds to 20-4 mA.
The adjustments (engineering unit and decimal point) selected for the
flow will be valid within this option.
The minimal difference between the flow rate at 4 mA and 20mA is
dependent on the position of the decimal point.
Number of decimals
Minimal flow difference
In case of electronic failure the device will emit an error signal of 22 mA.
The figure below shows an example of relationship between the 4-20mA output and the
associated measuring range
Figure 4.1 - Output Signal
8045
CALIBRATION
0
2
Enter the beginning of the
measuring range
mA
20
4
20
1
2
0,2
0,11
180
25
3
0,101
Enter the end of the
measuring range
Real Flow