Motor connection
Fig.9-8
Cable cross-sections for the motor connection
Type
EVF9381-EV
EVF9381-EVxxxx
EVF9382-EV
EVF9382-EVxxxx
EVF9383-EV
EVF9383-EVxxxx
EDKVF9383 DE/EN/FR 1.0
0
U
V
W
BR1
BR2
PE
40 mm
2
M8
25-30 Nm
U, V, W
M6
221-264 lb-in
PE
15-20 Nm
133-176 lb-in
Motor connection example
BR1, BR2
Brake resistor can only operated with the variants V060, V110, V270 and V300
For connection see System Manual of 9300 vector
Master terminals
Slave terminals
Connect the motor cable shield with a surface as large as possible to the control
cabinet mounting plate by using the clamps.
Conductive surface
Ensure to have the poles right!
Do not exceed the maximum motor cable length!
1)
Multiple conductor; both conductors must have the same cross-section
Observe the national and regional legislation
Electrical installation
1
BR1
BR2
PE
max.
40 mm
300 mm
2
3
M6
PE
15-20 Nm
133-176 lb-in
Installation to EN 60204-1
2
U, V, W [mm
]
Master
Slave
150
150
1)
2 × 50
2 × 50
150
150
1)
2 × 50
2 × 50
240
240
1)
2 × 95
2 × 95
Motor connection
U
V
W
max.
300 mm
3
M8
25-30 Nm
U, V, W
221-264 lb-in
2
PE [mm
Master
Slave
95
1)
95
1)
150
1)
4
9300VEC036
]
95
95
150
69