The country set must always be the same as the country where the inverter is installed. This
n
causes the inverter to load the prescribed grid parameters for the selected country; more infor-
mation on this is provided in the
The country can only be set once!
n
Contact your installer if you have set the wrong country.
Contact your installer if you cannot select the country where your inverter is installed.
n
The country setting does not affect the language used on the display. The display language is
n
set separately.
4.7.2
Operation
Starting initial commissioning
747.431 | Z08 | 2014-01-31
country table below.
✔ The check list for initial commissioning is displayed:
The default display language is English.
n
The Language entry is selected.
n
The check boxes are not selected.
n
———————————————————————————
NOTICES
When a check list item is called up the corresponding
n
check box is automatically selected.
The following items are only displayed when the use of a
n
reactive power characteristic curve is prescribed for the
country currently selected in the Country item:
–
Reac. pwr. ch. c. (type of reactive power char-
acteristic curve)
–
No. of nodes
–
1)
Node 1
1)
–
Node 2
–
1) 2)
Node n
–
Display char. curve
1)
: Is only displayed for reactive power characteristic
curve type Enter char. curve.
2)
: Is only displayed when no. of nodes has been set
to a value > 2.
Initial commissioning is completed by calling up the
n
Finish item.
Finish can only be performed when
n
boxes are selected.
———————————————————————————
1. Press rs to select a check list item.
2. Press SET to call up the item.
The items are described in detail below.
1)
all other check
GB
109