5. Appendices
EX RT CLA module
AC input voltage: 160-280 Volts AC,
z
Input frequency: 40-70 Hz,
z
Battery charge current: 6 A DC,
z
z
Recharge time to recover 90% of the rated backup time after discharge at full load:
EX RT 5
EX RT 7
EX RT 11
Thermal characteristics
z
The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20
to +25°C range.
Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at
z
temperatures under 10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery
manufacturers no longer guarantee operation due to the risk of thermal runaway.
Air enters through the front and exits through the back.

5.2 Glossary

Backup time
Bypass AC source
ECO mode
Load
Manual bypass
Normal (double conversion) mode
Normal AC source
Relay contacts
UPS
Page 38 - 34007724EN/AD
Configuration for
2 hours backup time
5 hours
5 hours
7 hours
Time that the connected loads can operate on battery power.
Source supplying the bypass line. The load can be transferred to the bypass line if
an overload occurs on the UPS output, for maintenance or in the event of a
malfunction.
Operating mode by which the load is supplied directly by the AC source if it is
within the tolerances defined by the user. This mode reduces the consumption of
electrical power.
Devices or systems connected to the UPS output.
Rotary switch controlled by the user, used to connect the loads directly to the
AC source.
Transfer of the load to the manual bypass enables UPS maintenance without
interrupting the supply of power to the connected loads.
The normal UPS operating mode in which the AC source supplies the UPS which
in turn supplies the connected loads (after electronic double conversion).
Normal source of power for the UPS.
Contacts supplying information to the user in the form of signals.
Uninterruptible Power Supply.
Configuration for
4 hours backup time
12 hours
12 hours
15 hours
Configuration for
8 hours backup time
20 hours
20 hours
24 hours