5.1 Technical specifications

Electrical characteristics

I/T network and industrial operating modes
Overload, and Bypass
AC source in tolerance.
Overload, and Bypass
AC source not in
tolerance.
Output short circuit and
Bypass AC source in
tolerance.
Output short circuit and
Bypass AC source not
in tolerance.
Selection of protection devices
UPS unit with common Normal and Bypass AC inputs
Bypass AC
Normal AC
UPS unit with separate Normal and Bypass AC inputs
Bypass AC
Normal AC
When sizing the upstream circuit breakers, the parameters presented below must be taken into account:
Line current values
power rating
5 kVA
7 kVA
11 kVA
Discrimination of upstream/downstream protections mentioned in paragraph 2.6 is achieved for a 30 m
cable length and 10 mm
Circuit breaker capacity must be selected according to the installation, length and cross section of cables.
Mode Industrial mode
Same as I/T network mode, but the UPS
does not return to normal mode if overload
released.
Load is transfered to Bypass AC source
with 10 milliseconds output break. The
UPS does not return to normal mode if
overload released.
Load is transfered to Bypass AC source,
the UPS returns to normal mode if the
short circuit is released by downstream
circuit breaker action (see section 2.6).
The load is transfered to Bypass AC source
with 10 milliseconds output break. The
UPS does not return to normal mode if the
short circuit is released by downstream
circuit breaker action (see section 2.6).
Upstream
circuit breaker
(not supplied)
Upstream
circuit breaker
(not supplied)
Upstream
circuit breaker
(not supplied)
UPS
Continuous current
at 400/320 Volts
and nominal load
9/10 A
10/11 A
15/19 A
cross section.
2
11
Normal
AC source
Input
circuit
fuse
breaker
10
9
11
Normal
AC source
circuit
Input
breaker
fuse
10
9
Continuous current
at 320 Volts and
overload = 110 %
limited to 2 minutes
11 A
12 A
21 A

5. Appendices

I/T network mode
Load is transfered to Bypass AC
source.
UPS returns to normal mode if
overload released.
The UPS shuts down and load is not
transfered to Bypass AC source.
The load remains powered by the
UPS.
The UPS shuts down after 3 minutes
if the short circuit remains.
The load remains powered by the
UPS. The UPS shuts down after 3
minutes if the short circuit remains.
Downstream
circuit breaker
Output
(not supplied)
fuse
8
Downstream
Output
circuit breaker
fuse
(not supplied)
8
Input fuse rating
Output fuse rating
25 A
25 A
30 A
34007724EN/AD - Page 35
80 A
80 A
100 A