Herunterladen Inhalt Inhalt Diese Seite drucken

Battery Extensions For Ups Backup Times Up To 60 Minutes; Cla Module (Long Backup Time Charger) For Backup Times From 2 To 8 Hours - Eaton EX RT 7 Installationsaleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 80
Battery extensions for UPS backup times up to 60 minutes (at full load)
EX RT offers a standard backup time of 5/9 minutes at full load.
To increase backup time, it is possible to connect EX RT EXB 7/11 modules to the UPSs.
Battery extensions for EX RT 5, EX RT 7 or EX RT 11
EX RT 5/7
+ EX RT EXB 7 RT
/
EX RT 11
+ EX RTEXB 11
5 kVA:
7 kVA:
11 kVA:

CLA module (Long backup time charger) for backup times from 2 to 8 hours

(Part number 68004)
Very long backup times, from 2 to 8 hours at full load, require a EX RT CLA module.
EX RT CLA
~
Battery backup
time
2 hours
4 hours
8 hours
Total battery voltage : 240 V DC (20 x 12V DC).
The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalisation
section).
EX RT EXB 7
EX RT EXB 7
+
+
/
EX RT
EXB 11
9 min
26 min
7 min
20 min
5 min
14 min
EX RT 5/7/11
Recommended batteries for:
EX RT 5
EX RT 7
50 Ah
65 Ah
100 Ah
130 Ah
200 Ah
260 Ah
EX RT EXB 7
+
/
/
EX RT
EX RT
EXB 11
EXB 11
42 min
60 min
32 min
45 min
22 min
30 min
5 0 A
EX RT 11
100 Ah
200 Ah
400 Ah
1. Presentation
EX RT EXB 7
EX RT EXB 7
+
+
/
/
EX RT
EX RT
EXB 11
EXB 11
72 min
87 min
57 min
70 min
42 min
53 min
34007724EN/AD - Page 9