3. Operation

3.6 Shut down

OFF
18
Page 30 - 34007724EN/AD
15
LOAD LEVEL
4 kW / 5 kVA
ON
12
9
1 - Press the OFF button
18
The load is no longer protected by the UPS. It is
powered via the bypass AC source. If the UPS is set in
frequency converter mode, the load will not be
powered.
If the bypass AC source is out of tolerance, the UPS
will generate a 10 ms output calibrated break.
2 - Set the battery circuit breaker(s)
3 - Set the Normal AC source circuit-breaker
position.
4 - For a full shutdown of UPS and connected load, the
more than 3 seconds.
12
to the "0" position.
9
to the "0"