Reconnecting the power module
OFF
4.3 Hot-swapping the battery module
Disconnecting the battery module
29
28
Reconnecting the battery module
15
LOAD LEVEL
4 kW / 5 kVA
ON
21
29
28
12
Secure the Input/Output junction box using the three screws.
z
Reconnect the battery cables
z
module.
Switch the battery circuit breaker(s)
z
Switch the Normal AC source circuit-breaker
z
position.
z
Turn the manual bypass switch from the BYPASS to the
NORMAL position.
Check that the led
15
is on.
z
Follow initial start up sequence (see section 3.1) in order to
z
personalize the UPS.
z
Push the ON button
21
for more than 3 seconds.
The green led
is on, and the connected equipment is now
13
protected by the UPS.
Switch the battery circuit breaker(s)
z
Disconnect the battery cables
z
module.
The battery module can be replaced. The connected equipment
is powered by the UPS.
It is also possible to replace battery trays instead of battery
module.
Contact your nearest after sales support service.
To remove battery trays:
z
First, switch the battery circuit breaker(s)
position.
See section 2.3 and follow instructions to remove battery
z
trays.
Reconnect the battery cables
z
module.
z
Switch the battery circuit breaker(s)
To reconnect battery trays:
See section 2.3 and follow the reverse instructions.
When battery module front panel is closed, connect the
z
battery cables
and
to the power module.
28
29
Switch the battery circuit breaker(s)
z
4. Maintenance
and
to the power
28
29
12
to the "I" position.
to the "I"
9
12
to the "0" position.
and
from the power
28
29
12
to the "0"
and
to the power
28
29
12
to the "I" position.
to the "I" position.
12