4.1.23 Cooling option
This option activates the cooling of the
store by falling below the adjusted tem­
perature measured at the store sensor
S3 (store maximum temperature, see
4.1.23). The surplus heat is released to
the heating circuit.
Cooling function
Adjustment range: Yes ... No
Factory setting: No
4.1.24 Temperature - cooling function
The store is cooled after exceeding the
store maximum temperature T­Cooling by
activating the heating circuit pump.
T-Cooling
Adjustment range: 50 °C ... 90 °C
Factory setting: 90 °C
4.1.25 Minimum temperature limita-
tion
Activation / deactivation of the minimum
temperature limitation
Min.
Adjustment range: Yes ... No
Factory setting: No
4.1.26 Minimum temperature
The heating circuit is switched off as
soon as the measured temperature at the
boiler sensor S3 falls under the adjusted
minimum temperature.
T-Min.
Adjustment range: 20 °C ... 60 °C
Factory setting: 40 °C
4.1.27 Week timer heating period
Up to 21 time frames can be adjusted for
the heating period. Adjust the desired
switch­on and switch­off time (e.g. t1­on
= Mo, 22:00 and t1­off = Tues., 0:00 for
the first time frame).
If the switch­on and switch­off times are
identical, the timer is deactivated.
WTHop. / t1 (2/3)-on
Adjustment range: Mo, 00:00 .. Su, 23:45
Factory setting: Mo, 06:00
WTHop. / t1 (2/3)-off
Adjustment range: Mo, 00:00 .. Su, 23:45
Factory setting: Mo, 22:00
32
4.1.28 Week timer afterheating
Up to 21 time frames can be adjusted for
the afterheating. Adjust the switch­on
and switch­off time (e.g. t1­on and t1­off
for the first time frame). If the switch-on
and switch­off time are identical, the time
frame is deactivated.
WTRHop. / t1 (2/3)-on
Adjustment range: Mo, 00:00 .. Su, 23:45
Factory setting: Mo, 00:00
WTRHop. / t1 (2/3)-off
Adjustment range: Mo, 00:00 .. Su, 23:45
Factory setting: Mo, 00:00
4.1.29 DHW afterheating
Activation / deactivation of the DHW af­
terheating (reference sensor S6).
For module 1 only.
HW-RH
Adjustment range: Yes ... No
Factory setting: No
4.1.30 Switch-on temperature HW-RH
Switch­on temperature for the DHW af­
terheating.
T-HW-on
Adjustment range: 0 °C ... 89 °C
Factory setting: 45 °C
4.1.31 Switch-off temperature HW-RH
Switch­off temperature for the DHW af­
terheating.
T-HW-off
Adjustment range: 1 °C ... 90 °C
Factory setting: 55 °C
4.1.32 Timer for DHW heating
Up to 3 time frames can be adjusted for
the HW­RH.
Adjust the desired switch­
on and switch­off time (e. g. t1­HW­on
22:00 and t1-HW-off 0:00 for the first
time frame).
If the switch­on and switch­off time are
identical, the time frame is deactivated.
t1 (2/3)-HW-on/off
Adjustment range: 00:00 ... 23:59
Factory setting: 00:00