Parameters of the „Heat.loop 1(2/3)" menu of the SKSC3+ controller
4.1.1 Current flow temperature
Tflow
Display range: 30.0 °C ... 200.0 °C
4.1.2 Current outdoor temperature
Toutd.
Display range: 30.0 °C ... 200.0 °C
4.1.3 Current remote control correc-
tion
Man.corr.
Display range: 15.0 K ... 15,0 K
4.1.4 Current set flow temperature
Targ.flow
Display range: 20 °C ... 100 °C
4.1.5 Current heat source tempera-
ture S3
S3
Display range: 30.0 °C ... 200.0 °C
4.1.6 Current heat source tempera-
ture S4
S4
Display range: 30.0 °C ... 200.0 °C
4.1.7 Current store temperature HW-
RH
S6
Display range: 20 °C ... 100 °C
4.1.8 Night correction
Adjustment channel for night correction of
the heating circuit, in which the flow set
temperature is lowered by the the adjust
ed temperature difference.
Night corr.
Adjustment range: 40 K ... 0 K
Factory setting: 4 K
4.1.9 Day correction
Adjustment channel for the day correc
tion function of the heating circuit. The
day correction function is always activated
outside the 21 time frames of the night
correction function. The set flow tempera
ture is raised or lowered by the adjusted
temperature difference.
Day corr.
Adjustment range: 5 K ... 15 K
Factory setting: 0 K
30
4.1.10 Maximum flow temperature
Adjustment channel for the admissible
maximum flow temperature of the heat
ing circuit. If the maximum flow tem
perature is exceeded, the heating circuit
will be switched off (the mixer will close
and the pump will be switched off, see
4.1.21). The maximum flow temperature
has to be higher than the maximum pos
sible flow temperature resulting from the
selected heating curve (including day and
remote control correction).
Tflowmax
Adjustment range: 10 °C ... 100 °C
Factory setting: 50 °C
4.1.11 Heating curve
Dependance on the feed flow temperature
of the ambient temperature and the se
lected heating curve line.
HL 1,2,3 / Heating curve
Adjustment range: 0.3 ... 3.0
Factory setting: 1.0
110
100
2,1
90
1,8
80
1,5
70
1,2
60
0,9
50
40
0,6
30
0,3
20
-20
-15
4.1.12 Mixer runtime
The mixer regulation is used to equal the
flow temperature with the flow set value.
Therefore, the mixer is opened/closed
according to the deviation. The mixer is
activated for a certain time (factory set
ting 4 seconds). The pause is calculated
from the deviation from the set value and
measured value.
Mixer
Adjustment range: 1 sec ... 20 sec
Factory setting: 4 sec
GB
Heizkennlinien
-10
-5
0
5
10
15
20
Außentemperatur in °C