3.9 Blocking protection for heating
circuit pump:
The heating circuit pump is switched on
every day at 12 o´clock for 30 seconds.
Thus, pump blocking is avoided. This func
tion will only be suppressed if the set fl ow
temperature is reached, the fl ow sensor is
damaged or the DHW priority function is
active.
3.10 Antifreeze function:
If the temperature at the fl ow sensor falls
below 8 °C, the heating circuit is activated.
If the fl ow temperature reaches 10 °C, the
heating circuit is deactivated.
4
Operation and function
Connect the SKSCEM1 heating circuit
module(s) to the SKSC3+ main control
ler via the VBus. Activate the heating cir
cuit module(s) in the Options menu of the
controller. All adjustment and display val
ues are listed in the corresponding menu
(heating circuit 1,2,3)
ATTENTION: It is only possible to connect
the same type/software version of heating
circuit modules to a SKSC controller!
4.1
Control parameters and display channels
SKSCEM1 heating circuit module display channels
• S1 Sensor 1
Current heating circuit fl ow sensor (S1)
• S2 Sensor 2
Current outdoor temperature sensor
(S2)
• S3 Sensor 3
Current afterheating store sensor 1
• S4 Sensor 4
Current afterheating store sensor 2
• S5 Sensor 5
Current setting of the remote control
(S5)
• S6 Sensor 6
HW afterheating sensor
28
3.11 Store afterheating (Differential
control):
For the afterheating of the store, the dif
ference between the calculated fl ow set
temperature and one or two reference
sensors at the store/buffer is measured. If
the difference between both temperatures
is too small, the afterheating is activated.
The afterheating switches off when the dif
ference between store and fl ow set tem-
perature is high enough.
Sonnenkraft SKSCEM1
• EC Error Code
Error code
0 = OK
1 = Sensor fault
2 = Bus fault
• VC
(Version Compatibility)
Recognition of the SKSCEM1 heating
circuit module by the controller. 4 =
SKSC3
• SA Sub Address
Sub address adjustment channel for
the operation of several heating circuit
modules (see 6. Commissioning)
• PG ProGram
Program version of the hardware
• VN VersioN
Version numer of the software
GB