11.2 Supply voltage
1 × 220-240 V -10 % / +10 %, 50/60 Hz -2 % / +2 %, PE.
11.3 Overload protection
The overload protection of the E-motor has the same characteristic
as an ordinary motor-protective circuit breaker. As an example, the
E-motor can stand an overload of 110 % of rated current for 1
minute.
11.4 Cable requirements
DANGER
Electric shock
Death or serious personal injury
‐
Comply with local regulations as to cable cross-
sections.
‐
Use the recommended fuse size.
1 × 200-230 V
Power [kW]
0.25 - 2.2
Conductor types
Stranded or solid copper conductors.
Conductor temperature ratings
Temperature rating for conductor insulation: 60 °C (140 °F).
Temperature rating for outer cable sheath: 75 °C (167 °F).
11.5 Accessories
The following are the communication interface modules intended for
use with the product:
Protocol
GENIbus
LonWorks (Single)
PROFIBUS DP
Modbus RTU
BACnet MS/TP
Modbus TCP, BACnet IP,
PROFINET, GiC/GRM IP,
EtherNet IP
LonWorks (Multi)
Installing a communication interface module not listed above might
affect the compliance level of the product.
16
Cross-section
2
[AWG]
[mm
]
1.5 - 2.5
16-12
Communication interface
module
CIM 050
CIM 100
CIM 150
CIM 200
CIM 300
CIM 500
CIM 110
12. Further product information
Use either the QR code or the web address below to access
the complete installation and operating instructions for the relevant
product.
CRE, CRIE, CRNE, SPKE, MTRE and CME pumps
http://net.grundfos.com/qr/i/98358864
13. Disposing of the product
This product or parts of it must be disposed of in an environmentally
sound way.
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company or
service workshop.
The crossed-out wheelie bin symbol on
a product means that it must be
disposed of separately from household
waste. When a product marked with
this symbol reaches its end of life, take
it to a collection point designated by
the local waste disposal authorities.
The separate collection and recycling
of such products will help protect the
environment and human health.
See also end-of-life information at
recycling.
14. Document quality feedback
To provide feedback about this document, use your smart device to
scan the QR code.
Click here to submit your feedback
www.grundfos.com/product-