A B C Error
code
14 R 2 E14
15 R 1 E15
16 R 2 E16
60
Fault
Potential cause
Fire alarm
Fire or smoke sensor
Fire protection ther-
connected to this input
mostat connected to
is active
the air duct (access-
Nothing is connected to
ory)
this input
Input is normally
closed (NC), but now
it is open
High water level (ac-
The water drain is
cessory)
blocked
The water drain is
Water level is too
mounted incorrectly
high
Auxiliary drain pump is
not operating
Water level is not too
Water level sensor is not
high
connected
Water level sensor is
normally open (NO)
Digital input incorrectly
configured
Firmware 2.9 and
Fire protection control
later: FPC error (ac-
with this address has
cessory), only active
already been installed
if the accessory "fire
but is no longer access-
protection control" is
ible
connected to the
unit.
No communication
with fire protection
control
Missing position
A fire damper is closed
feedback for a fire
but should be open
damper
Failure during
Fire damper is jammed
monthly, weekly or
either in open or closed
manual fire damper
position
test
INSTALLATION AND SERVICE MANUAL FOR PROFESSIONALS
Maintenance and troubleshooting: Troubleshooting
Action required
Check for smoke or fire
Check if sensor and con-
nection are OK
Mount short circuit
equipment
Clean the water drain
Check whether the water
drain is mounted on the
correct side and make
sure that the pipes are
not located above the
level of the water drain
Check pump
Check fuse
Check wiring
Configure or change the
water level sensor so that
it is normally closed (NC)
Check the configuration
of the digital input with
PC Tool
Check connection to fire
protection control
Check the power supply
to the fire damper
Check internal fire de-
tector of the fire dampers
Something is blocking
the fire damper
Fire damper is incorrectly
connected
Defective fire damper
Reset
The alarm indicator
can be reset by
pressing the alarm
button or by switch-
ing the unit off/on.
However, the unit
cannot be started
until the causes of
the alarm have been
eliminated
Automatic reset
when the input is
closed again
Manual reset by
pressing the alarm
button or by switch-
ing the unit off/on