Installation

General requirements

Installation site
and directing the
air duct
connections
Allow for
additional space
Space
requirements for
ceiling mounting
32
The following should be considered when selecting an appropriate installation site:
1. The unit is intended for installation in dry environments at temperature levels >12 °C, e.g.
in utility rooms or rooms with similar heating requirements.
2. The unit can be mounted vertically or horizontally on a wall or horizontally on the ceiling.
Before carrying out the installation, please ensure that the ceiling or wall structure is able
to support the additional weight of the unit.
3. The direction of the airflow can be switched electronically, offering the option to direct
the connected duct system either to the right or to the left. Further information on
changing the operating mode can be found on page 36.
This unit is designed to be used in concealed installations.
Please provide for additional space:
• To replace the unit if necessary.
• For the installation of an external preheater (accessory), which is mounted from the
outside into the duct system within the area of the incoming outdoor air at T1.
• For checking and testing drain hoses, even if no preheater is installed.
These requirements are also to be observed by the customer service if the unit has to be
completely dismantled due to maintenance purposes. Any warranty claims can only be
acknowledged if the aforementioned requirements are fulfilled. See the minimum dimensions
below for the space required for wall or ceiling mounting.
If you install the unit under the ceiling, please allow enough space on both sides to screw the
screws properly into the ceiling. Please also allow for additional space on the side of the unit
with the control panel.
80
Fig. 17: Space requirements for ceiling mounting
INSTALLATION AND SERVICE MANUAL FOR PROFESSIONALS
945
900
Installation: General requirements