INSTALLATION AND SERVICE MANUAL FOR PROFESSIONALS
Maintenance and troubleshooting: Troubleshooting
A B C Error
Fault
code
3 R 0 E3
Bypass damper does
not close as expec-
ted
Bypass damper
Reduced heat recov-
ery due to low ex-
tract airflow
Bypass is closed, but
supply air temperat-
ure is lower than ex-
pected
Airflows are not bal-
anced. There is much
more extract air than
supply air
4 R 1 E4
Extract air temperat-
ure sensor (T1)
Control board meas-
ures that temperat-
ure sensor is open or
short-circuited
Potential cause
Action required
Switch position A: by-
Check whether bypass is
pass is closed, but sup-
activated in PC Tool
ply air temperature is
Check if bypass is
lower than expected
blocked
Switch position B: by-
Check mechanical con-
pass is closed, but ex-
nection between bypass
haust air temperature is
actuator and bypass
higher than expected
valve
Check electrical connec-
tion between control unit
and bypass
Check control unit output
Extract air filter soiled
Changing the filter
Poor adjustment of the
Adjust the system
airflows
A bathroom extract air
Remove the extract air
fan creates a negative
fan from the bathroom
pressure in the dwelling
and connect the extract
air from the bathroom to
the ventilation system in-
stead
A kitchen extract air fan
Provide heated fresh air
is creating negative
for the extraction hood. If
pressure inside the
this cannot be achieved,
dwelling
open a window/door
while the extraction hood
is running
A stove fan creates neg-
Contact the fireplace/
ative pressure inside the
stove supplier to take
dwelling
safety precautions
Supply air filter is soiled Changing the filter
Poor adjustment of the
Adjust the system
airflows
Temperature sensors
Mount temperature
are not mounted cor-
sensor(s) correctly
rectly
Resistance in one of the
Replace temperature
temperature sensors is
sensor
too low or too high
Resistance in temperat-
Replace control board
ure sensor is OK
Reset
Automatic reset
when efficiency is
high enough for
30 seconds
Automatic reset
when efficiency is
high enough for
30 seconds
Automatic reset if
the temperature is
within the normal
range for 30 seconds
57