Herunterladen Inhalt Inhalt Diese Seite drucken

Dantherm RCC 130 Bedienungsanleitung Seite 44

Übersetzung der originalbetriebs- und serviceanleitung
Vorschau ausblenden Andere Handbücher für RCC 130:
Inhaltsverzeichnis
Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 129
Ceiling mounting
Connecting the
duct system
44
5. Before tightening the four screws firmly, push the unit to the left so that all the screws are
seated in the right part of the mounting bracket slots.
6. Connect the air ducts according to the description in the chapter Installation options.
7. Connect the hose of the condensate drain.
Please proceed as follows to mount the unit horizontally on the ceiling:
1. Place the unit in a suitable position on the ceiling (see page 32).
2. Drill two holes into the left mounting bracket, insert the appropriate screws and tighten
them lightly.
3. Drill two holes into the right mounting bracket, insert the appropriate screws and tighten
them lightly.
x 2
4. Before tightening the four screws firmly, push the unit to the left so that all the screws are
seated in the right part of the mounting bracket slots.
5. Connect the air ducts and the drain hose.
Only connect the air ducts to connections with spigots (specifications in accordance with local
regulations).
NOTICE
NEVER screw duct spigots directly into the sheet metal of the unit.
Fig. 35: Correct connection of the air ducts
Insulate the air ducts in accordance with local requirements, taking into account the ambient
temperature of the installation.
INSTALLATION AND SERVICE MANUAL FOR PROFESSIONALS
Installation: Assembly