Name
Settings
Logic gate
inactive
1 ... 2
1 ... 2: the selected number of logic gates with the associated parameters is
additionally available.
inactive: the logic gate output is not available.
Remote control
inactive
Program
User
Program and user
Inactive: the IR receiver integrated in the detector is deactivated.
Program: enables service personnel to change a number of detector para-
meters (e.g. ON delay, stay-on times and light-level settings) with a special
IR remote control without using ETS.
User: enables the room user to operate and dim lighting, save and select as
many as 4 scenes as well as re-activate (enable) light-level control with a small
IR remote control.
Program & user: enables switching, dimming and scene control
as well as the changing of detector parameters by IR remote control.
10.2 Sensor settings
Name
Settings
Boost factor
1 ... 100 %
(HF & US only)
This parameter can be used for setting reach of US and HF presence detec-
tors in 1 % increments.
Sensitivity
1 ... 100 %
If a low sensitivity setting is selected, several movement triggers will be nec-
essary to initiate movement detection. In the event of inadvertent triggering,
this function can be used for filtering out brief non-recurring interference
signals. Unlike the boost factor, this setting does not reduce reach.
First presence
US and IR
US or IR
(DualTech only)
IR
US
This parameter is used for selecting the technology(ies) required for initial
detection for switching light on.
Maintain presence
US and IR
US or IR
(DualTech only )
IR
US
This parameter is used for selecting the technology(ies) required for maintain-
ing presence (retriggering).
10.3 Light output 1..4
Name
Settings
Object light output
ON/OFF
Dimming level
Scenario
This parameter is used to select which object the output sends with.
ON level in percent
0 % ... 100 %
This parameter is used to select which dimming level to send
for the ON state.
OFF level in percent
0 % ... 100 %
This parameter is used to select which dimming level to send
for the OFF state.
Factory setting
Name
inactive
Send switching object
This parameter is used to select whether to send the ON and OFF switching
commands for the dimming level object or whether to send only ON or only
OFF.
inactive
Switch ON scene
This parameter is used to select which scene to send for the ON state.
Switch OFF scene
This parameter is used to select which scene to send for the OFF state.
Send status cyclically
This parameter is used for selecting whether the output not only sends after
any change but also cyclically and, if so, for which status.
Do not send status cyclically: no status is sent cyclically.
ON/OFF: ON and OFF status is sent cyclically
ON: only ON status is sent cyclically.
Factory setting
OFF: only OFF status is sent cyclically.
100 %
Interval for sending cy-
clically
Time interval for sending at cyclical intervals.
The maximum time interval is 18:12:15.
100 %
Light output mode
This parameter is used for selecting whether to switch the light output ON
and OFF automatically in relation to presence and light level (fully automatic
US or IR
operation) or whether only to switch it OFF automatically (semi-automatic
operation).
Stay-ON time, IQ mode
This parameter is used to define whether to select the stay-ON time for the
light output via a parameter (inactive) or whether the stay-ON time of be-
tween 5 and 20 minutes is to be automatically and continually matched to
US or IR
room usage via the IQ mode (active).
Light output stay-ON
time
Stay-ON time is started if no presence is detected. This has the purpose of
preventing the output from switching OFF immediately if the room is vacated
for a short time and having to be switched back ON again when a person
returns to the room.
Stay-ON time can be set from 00:00:10 to 18:12:15.
Slave input
Factory setting
ON/OFF
This parameter defines whether the slave input expects an ON
telegram or an ON and OFF telegram.
Light level
100 %
Daytime operation
Setting to define whether light output is to be switched irrespective of light
0 %
level.
Light-level sensor ON
This parameter is used to define which light-level measurement the sensor
compares its switching threshold with.
Initial level, light-level
sensor, external
This parameter is used to define which value the sensor works with until the
first value is received via the KNX bus.
- 36 -
KNX Application Description for Control Pro Series
Settings
ON/OFF
ON
OFF
1 ... 64
1 ... 64
Do not send status cy-
clically
ON/OFF
ON
OFF
hh:mm:ss
automatically
ON and OFF
automatically OFF only
Active
Inactive
hh:mm:ss
inactive
ON
ON/OFF
Yes
No
Internal
External
2 lux ... 1000 lux
Factory setting
ON/OFF
1
2
00:00:30
automatically
ON and OFF
inactive
00:05:00
ON
NO
Internal
200