en
5 Configuration
Tab.52
Number of boards present in the appliance
Object instance
Data Type
128
UINT8
Tab.53
Specific error code per board
Board 1
2
3
129
135
141
532
534
536
533
535
537
5.12
Fallback scenario
Tab.54
Fallback scenario Modbus registers
Modbus register
21020
21021
21022
21023
26
Description
Devices connected
You can use the next table to find the object instance for the error code of
the specific device.
4
5
6
147
153
159
538
540
542
539
541
543
Set a fallback scenario if there is no communication between the gateway
and the BMS. You can keep, adjust, or cancel the heat demand with the
scenarios in the following table.
Data Type
Description
ENUM8
The BMS fallback heat de
mand mode
ENUM8
BMS fallback heat de
mand configuration
UINT8
BMS fallback heat de
mand period
UINT8
The power setpoint
Resolution / Format Min - Max
1 Units
7
8
Description
165
171
Type of device
544
546
Error code
545
547
Error custom code
matrix
If the device type shows code 0x0008, it means it is a CU-GH08.
Resolution / Format
0: BMS fallback HD mode
1: Use Fallback HD
0: Cancel directly
1: Never cancel
2: Maintain fallback HD
1, minute
%
Access
0 - 16
R
Resolution /
Format
[0xZZYY]
ZZ = Device
category
YY = number
in the catego
ry
00: CU-GH
01: CU-OH
02: EHC
14: MKI
19: SCB
1B: EEC
1E: Gateway
0xFFFF: No
error
0xFFFE: De
vice not avail
able
Other: Specif
ic error
0: Locking
3: Blocking
6: Warning
Min - Max
0 – 1
0 – 2
0 - ....
0 – 100
7854678 - v.01 - 15092023
Min-
Ac
Max
cess
R
R
R
Access
R/W
R/W
R/W
R/W