5.8.4
Zone counters
Tab.34
Zones
Modbus
Data
Description
register
type
1115
UINT32
Numbers of pump operating hours of the
zone
1117
UINT32
Numbers of times the pump of the zone
has started
Tab.35
All main zones counter registers
Zone
1
2
CC00X
1115
1627
CC01X
1117
1629
5.8.5
Set temperature without outdoor temperature sensor
Tab.36
Mode for the zone with display code CP32X or DP200
Zone
Address
Zone 1
649
Zone 2
1161
Zone 3
1673
Zone 4
2185
Zone 5
2697
Zone 6
3209
Zone 7
3721
Zone 8
4233
Zone 9
4745
Zone 10
5257
Zone 11
5769
Zone 12
6281
Tab.37
Temperature of the zone with display code CP01X
Zone
Address
Zone 1
648
Zone 2
1160
Zone 3
1672
Zone 4
2184
Zone 5
2696
Zone 6
3208
Zone 7
3720
Zone 8
4232
Zone 9
4744
Zone 10
5256
Zone 11
5768
Zone 12
6280
7854678 - v.01 - 15092023
3
4
5
2139
2651
3163
2141
2652
3165
If there is no outdoor or room temperature sensor in the system, you can
set a temperature for a zone.
Bytes
Data Type
2
UINT8
Bytes
Data Type
2
UINT16
Resolu
Min - Max
tion /
Format
1 Hours
0 - 4294967295
1 Units
0 - 4294967295
6
7
8
3675
4187
4699
3677
4189
4771
Description
Operating mode of the
zone
Description
Zone flow temperature
setpoint, used when the
zone is set to a fixed flow
setpoint.
5 Configuration
Access
Display code
R
CC001
R
CC010
9
10
11
5211
5723
6235
5213
5725
6237
Resolution / Format
0: Scheduling
1: Manual
2: Off
Resolution / Format
0,01 °C
en
12
6747
6749
Access
R/W
Access
R/W
19