5.8.7
Room temperature control in a zone
Tab.42
Zone control registers display: CP32X or DP200
Zone
Address
Zone 1
649
Zone 2
1161
Zone 3
1673
Zone 4
2185
Zone 5
2697
Zone 6
3209
Zone 7
3721
Zone 8
4233
Zone 9
4745
Zone 10
5257
Zone 11
5769
Zone 12
6281
Tab.43
Zone control registers for display: CP20X
Zone
Address
Zone 1
664
Zone 2
1176
Zone 3
1688
Zone 4
2200
Zone 5
2712
Zone 6
3224
Zone 7
3736
Zone 8
4248
Zone 9
4760
Zone 10
5272
Zone 11
5784
Zone 12
6296
Tab.44
Example for setting zones
Use case
Modbus register
I want to set zone 1 manually
to 20 °C
7854678 - v.01 - 15092023
After a heat demand, the appliance adjusts the temperature of the zone. If
an outdoor temperature sensor or the room unit is present, the
temperature will be based on the heating curve.
Bytes
Data Type
2
ENUM8
Bytes
Data Type
2
UINT16
649
1
Important
This is only possible if the room sensor or outdoor temperature
sensor is connected.
In this case the influence of the outdoor temperature sensor is
used.
Description
Operating mode of the
zone
Description
Manually setting the room
temperature setpoint of
the zone
664
200
5 Configuration
Resolution / Format
0: Scheduling
1: Manual
2: Off
Resolution / Format
0,1 °C
Comment
The zone will stay on 20 °C
until you change the tempera­
ture, or you set the zone back
to 0 (Scheduling)
en
Access
R/W
Access
R/W
21