The desired function must be activated in the pump,
see also chapter 4.3.
DP interface for an integratable double-pump ma-
x
nagement with the functions:
Addition operation (optimum efficiency peak-load
x
operation)
Automatic fault-activated changeover
x
Duty/Standby mode:
x
Basic load pump swap after 24 hrs of accumulated
x
operating time
The terminals are locked.
x
9.1.2 Terminal assignment of the Stratos IF
modules and cable specification
(Figure 14)
Serial digital interface PLR for connecting to inter-
x
face converter or proprietary coupling modules:
Terminal cross-section: max. 2,5mm
Bus cable:
Max. cable length:
Serial digital interface LON for connecting to LON-
x
WORKS networks:
Terminal cross-section: max. 2.5 mm
Bus cable:
Max. cable length:
Input for potential-free closed contact with the
x
function Ext. Off
max. cable length: 100 m, 2-core cable, shielded
Terminal cross-section:
Input for potential-free closed contact with the
x
function Ext. Min:
max. cable length: 100 m, 2-core cable, shielded
Terminal cross-section:
Output as potential-free opened contact with the
x
function SBM:
For latest prices and delivery to your door visit MyTub Ltd - 0845 303 8383 - www.mytub
52
2
2
min. 2 x 0,34mm
, shielded,
(z.B. J-Y(ST)Y 2x2x0,8mm
500m
2
2
min. 2 x 0.34 mm
, drilled
(10 t/m), shielded
(e.g. J-Y(ST)Y 2x2x0.8 mm
-750 m for bus topology
with max. 3 m long stub ca-
bles
-500 m for free topology,
with max. 320 m between 2
intercommunicating nodes
The indicated cable lengths
are dependent on the used
cable typ.
2
max. 1,5 mm
max. 1,5 mm
2
max. cable length: 100 m, 2-core cable, not shiel-
ded
Terminal cross-section:
Control input 0...10V:
x
max. cable length: 25 m, 2-core cable, shielded
Terminal cross-section:
DP interface
x
max. cable length: 2.5 m, 2-core cable, not shielded
Terminal cross-section:
9.2
Combination possibilities of the IF
modules for double-pump operation
Double pumps or two corresponding single pumps can
be retrofitted with a built-in double pump manage-
ment facility.
Stratos IF modules: Two IF modules linked together
x
via the DP interface are required to allow the pumps
to communicate with each other. In addition to dou-
ble-pump management, the IF modules provide ot-
her interfaces for the double pump, see also chapter
9.1.1.
Conditions: A double pump or two corresponding
x
single pumps are available.
When put into service, a master and slave
are defined, see also chapter4.3.
ATTENTION!
2
)
2
)
max. 1,5 mm
max. 1,5 mm
max. 1,5 mm
Stratos IF modules
Ext.Min, Ext.Off, SBM
max. 2.5 mm
Stratos IF modules
PLR, LON
A single pump that does not exist as
a double pump type cannot be confi-
gured as a double pump.
2
2
2