Part name
15
Input 2 (ECO mode) (*)
16
Common line
17
Input 3 (Swimming pool) (*)
18
Input 4 (Solar) (*)
19
Input 5 (Smart function) (*)
20
Input 6 (DHW boost) (*)
21
Input 7 (Power meter)
22
Aquastat security for circuit 1
(WP1)
23
24(C) Mixing valve close
25(O) Mixing valve open
26(N) Common line
27(L) Water Pump 2 (WP2)
28
Auxiliary power
29
30(N)
Electrical Heater DHW Output
31(L)
32(C) 3‑way valve for DHW tank
33(L) Line
34(N) Common line
Output 1 (3‑way valve for
35(C)
swimming pool) (*)
Output 2 (Water pump 3 (WP3))
36(L)
(*)
37
Output 3 (Auxiliary boiler or
electric heater) (*)
38
39
Output 4 (Solar) (*)
40

NOTE
(*): Inputs and outputs explained in the table are the factory‑set options. By means of the unit
PMEN0647 rev.0 - 11/2023
Available signal which allows to reduce the water setting temperature of
circuit 1, circuit 2 or both.
Terminal Line common for inputs 3, 4, 5, 6, 7.
Only for swimming pool installations: It is necessary to connect an
external input to the air to water heat pump to provide signal when the
water pump of swimming pool is ON.
Available input for Solar combination with Domestic Hot Water Tank.
For the connection of an external tariff switch device to switch OFF the
heat pump during peak electricity demand period. Depending on the
setting, the heat pump or DHWT will be blocked when signal is open/
closed.
Available input for an instantaneous heating of the domestic hot water of
the tank.
The measuring of the real power consumption can be done connecting
an external power meter. The number of pulses of the power meter is
a variable which must be set. By this, every pulse input is added into
corresponding operation mode (Heating, Cooling, DHW Operation). Two
possible options:
‑ One power meter for all installation (IU+OU).
‑ Two separated power meters (one for IU and one for OU).
Terminals intended for the connection of the Aquastat security accessory
(ATW‑AQT‑01) for controlling water temperature of the circuit 1.
When a mixing system is required for a second temperature control, these
outputs are necessary to control the mixing valve.
Terminal line common for mixing valve and water pump 2.
When there is a second temperature application, a secondary pump is the
circulating pump for the secondary heating circuit.
Power supply for ATW‑RTU and central device
If DHW tank contains an electric heater, the air to water heat pump
can activate it if the heat pump cannot achieve the required DHW
temperature by itself.
The air to water heat pump can be used to heat DHW. This output will be
ON when DHW is activated.
Line terminal for the 3‑way valve for DHW tank and swimming pool.
Terminal line common for 3‑way valve of DHW tank and outputs 1 and 2.
The air to water heat pump can be use to heat swimming pool. This
output will be ON when swimming pool is activated.
When there is a hydraulic separator or buffer tank, additional water pump
(WP3) is needed.
The boiler can be used to alternate with the heat pump when the heat
pump cannot achieve the required temperature by itself.
A water electric heater (as accessory) can be used to provide the
additional heating required on the coldest days of the year.
Output for solar combination with Domestic Hot Water Tank.