YUTAKI SERIES

Werbung

Inhaltsverzeichnis
loading

Inhaltszusammenfassung für Hitachi YUTAKI Serie

  • Seite 1 YUTAKI SERIES...
  • Seite 3 Specifikationerna i den här handboken kan ändras utan föregående meddelande för att HITACHI ska kunna leverera de senaste innovationerna till kunderna. Vi på Hitachi gör allt vi kan för att se till att alla specifikationer stämmer, men vi har ingen kontroll över tryckfel och kan därför inte hållas ansvariga för den typen av fel.
  • Seite 4 C A U T I O N This product shall not be mixed with general house waste at the end of its life and it shall be retired according to the appropriated local or national regulations in a environmentally correct way. Due to the refrigerant, oil and other components contained in heat pump, its dismantling must be done by a professional installer according to the applicable regulations.
  • Seite 5 Important note: Please, check, according to the model name, which is your heat pump system, how it is abbreviated and referred to in this instruction manual. MODELS CODIFICATION This Installation and Operation Manual is related to YUTAKI Units. Nota importante: compruebe, de acuerdo con el nombre del modelo, el tipo de bomba CODIFICACIÓN DE de calor, su abreviatura y su referencia en el presente manual de instrucciones.
  • Seite 7: Inhaltsverzeichnis

    General Index 1 GENERAL INFORMATION ....................1 General information ..........................1 1.1.1 General notes ..............................1 1.1.2 Introduction ..............................1 1.1.2.1 Overview of YUTAKI system ......................1 1.1.2.2 Summary of operations ........................2 Applied symbols ............................4 Product guide ............................5 1.3.1 ...
  • Seite 8 3.3  General specifications ........................... 33 3.3.1 Considerations .............................. 33 3.3.2 Split system - Outdoor unit ..........................33 3.3.3 Split system - Indoor unit ..........................36 3.3.3.1 YUTAKI S ............................36 3.3.3.2 YUTAKI S COMBI ..........................39 3.3.3.3 YUTAKI S80 ............................. 45 3.3.4 Monobloc system - YUTAKI M........................
  • Seite 9 5.1.3.2 Indoor unit for integrated tank version ....................82 5.2  Refrigerant cycle and hydraulic circuit for Monobloc system - YUTAKI M ..........83 6 REFRIGERANT AND WATER PIPING ................85 Refrigerant circuit ..........................85 6.1.1 Refrigerant piping ............................85 6.1.2  Precautions in the event of gas refrigerant leaks ..................86 6.1.3 Water piping ..............................87 6.1.4 Water quality (Preliminary information) ....................... 90 6.1.5 ...
  • Seite 10 8.5.1.4  Examples of possible configurations ....................124 8.5.1.5  Not allowed configurations ......................129 8.5.2  Advanced Configuration ..........................129 8.5.2.1 Screen 1 ............................129 8.5.2.2 Screen 2 ............................129 8.5.2.3 Screen 3 ............................130 8.5.2.4 Screen 4 ............................130 Menu navigation ..........................131 8.6.1 Operation information ..........................131 8.6.1.1 General ............................
  • Seite 11 8.6.5.1 System Information ........................166 8.6.5.2 Contact Information ........................166 8.6.6 Factory Reset ............................167 8.6.7 Return to user mode ..........................167 INDEX OF REFERENCES ........................168 9 TROUBLESHOOTING ....................171 10 MAINTENANCE ......................174 10.1 Maintenance work ..........................174 10.1.1 ...
  • Seite 13: General Information

    © Copyright 2016 HITACHI Air Conditioning Products Europe, S.A.U. – All rights reserved. No part of this publication may be reproduced, copied, filed or transmitted in any shape or form without the permission of HITACHI Air Conditioning Products Europe, S.A.U.
  • Seite 14: Summary Of Operations

    Two different models have been designed for different purposes: one model for space heating only and the other one for space heating as well as for DHW operation. For DHW operation (optional), HITACHI offers two specific YUTAKI S80 DHW tanks (DHWS200S-2.7H2E and DHWS260S-2.7H2E) which may be placed on top of the indoor unit or besides it, as an integrated unit to...
  • Seite 15 GENERAL INFORMATION Space cooling YUTAKI units can also be operated in cooling operation The dedicated “Cooling kit” accessory has been designed for this purpose. Combining the heating only models with these cooling kits, the reversible models become available. In this case, combination with fan-coils, refreshing floor or both (2nd temperature area) can be applied.
  • Seite 16: Applied Symbols

    GENERAL INFORMATION 1.2 APPLIED SYMBOLS During normal heat pump system design work or unit installation, greater attention must be paid in certain situations requiring particular care in order to avoid damage the unit, the installation or the building or property. Situations endangering the safety of those in the surrounding area or to the unit itself are clearly indicated in this manual.
  • Seite 17: Product Guide

    GENERAL INFORMATION 1.3 PRODUCT GUIDE 1.3.1 Classification of the units 1.3.1.1 Split system - Outdoor unit Unit type: Outdoor unit (Split air system) Position-separating hyphen (fixed) Compressor power (HP): 2, 2.5, 3, 4, 5, 6, 8, 10. For water combination Heat pump V: Single phase unit (1~ 230V 50Hz) —: Three phase unit (3N~ 400V 50Hz)
  • Seite 18: Monobloc System

    R-410A refrigerant R-134a refrigerant —: Type1: Version for operation in DHW with a remote tank W: Type2: Version for operation with Hitachi DHW tank Made in Europe Domestic hot water tank (For combination with YUTAKI S80 indoor unit standalone version)
  • Seite 19: Product List

    GENERAL INFORMATION 1.3.2 Product list 1.3.2.1 Split system - Outdoor unit 1~ 230V 50Hz 3N~ 400V 50Hz RAS-2WHVNP RAS-2.5WHVNP RAS-3WHVNP RAS-4WHVNPE RAS-4WHNPE RAS-5WHVNPE RAS-5WHNPE RAS-6WHVNPE RAS-6WHNPE RAS-8WHNPE RAS-10WHNPE 1.3.2.2 Split system - Indoor unit  YUTAKI S ( ) ( ) ( ) ( ) 1~ 230V 50Hz 3N~ 400V 50Hz RWM-2.0NE...
  • Seite 20 GENERAL INFORMATION  YUTAKI S COMBI N O T E Icons between brackets means possible extra operations to the factory-supplied operations. For cooling operation, refer to the Cooling kit accessory for YUTAKI S COMBI units. Standard model ( ) ( ) ( ) 1~ 230V 50Hz 3N~ 400V 50Hz RWD-2.0NWE-200S...
  • Seite 21 ( ) ( ) TYPE 1: Version for operation in DHW but with a remote tank TYPE 2: Version for operation with Hitachi DHW tank (Tank cannot be plugged on top of the unit) (Tank can be plugged on top of the unit or next to it)
  • Seite 22: Monobloc System

    • In “TYPE 2: Version for operation with Hitachi DHW tank”, the domestic hot water tank of model DHWS200S-2.7H2E or DHWS260S-2.7H2E is required. The DHW tank has to be ordered separately. The unit controller (PC-ARFHE) is factory supplied with the DHW tank (integrated in the front cover).
  • Seite 23: Accessory Code List

    GENERAL INFORMATION 1.3.3 Accessory code list Model Ref. For all series For YUTAKI S units For YUTAKI S COMBI units For YUTAKI S80 units For YUTAKI M units  Cooling kit accessories Accessory Ref. Name Figure Cooling operation kit for YUTAKI S (For 2.0-3.0HP) ATW-CKS-01 Cooling operation kit for YUTAKI S...
  • Seite 24 GENERAL INFORMATION Accessory Ref. Name Figure Wireless Intelligent thermostat for 2nd circuit (Only Room thermostat. For Intelligent thermostat application) ATW-RTU-06 MODBUS gateway for YUTAKI units ATW-MBS-02 KNX interface for YUTAKI units ATW-KNX-02 TaHoma gateway for YUTAKI units ATW-TAG-02 Auxiliary output signal box (Relay board for additional output signals) ATW-AOS-02 Kit for 4-20 mA application...
  • Seite 25 GENERAL INFORMATION  Temperature sensor accessories Accessory Ref. Name Figure 2nd. outdoor temperature sensor ATW-2OS-02 Indoor wired temperature sensor ATW-ITS-01 ATW-WTS-02Y Universal water temperature sensor  Water circuit accessories Accessory Ref. Name Figure 2nd zone mixing kit (Integrable in YUTAKI S COMBI 200 L model) ATW-2KT-03 2nd zone mixing kit (Wall mounted model)
  • Seite 26 GENERAL INFORMATION Accessory Ref. Name Figure ATW-AQT-01 Aquastat security (for heating floor protection) 3-way valve ATW-3WV-01 (Internal thread and spring return) ATW-WCV-01 Water check valve WEH-6E Water electric heater ATW-DPOV-01 Differential pressure overflow valve Flexible pipe ATW-FWP-03 PMML0335A rev.1 - 04/2016...
  • Seite 27: General Safety Notes

    If this is not the case, contact your distributor. • HITACHI pursues a policy of continuous improvement in product design and performance. The right is therefore reserved to vary specifications without notice. •...
  • Seite 28: General Data

    GENERAL DATA 3 GENERAL DATA 3.1 CAPACITY TABLES 3.1.1 Nominal capacity-performance tables 3.1.1.1 Considerations • The heating capacity tables show the capacity and performance data in integrated values (with defrost correction factor included). • The nominal heating and cooling capacities are based on the EN 14511 standard: Piping length: 7.5 meters; Piping lift: 0 meters. Keywords: •...
  • Seite 29 GENERAL DATA  YUTAKI S COMBI RAS-2 RAS-2.5 RAS-3 RAS-4 RAS-5 RAS-6 Outdoor unit model WHVNP WHVNP WHVNP WH(V)NPE WH(V)NPE WH(V)NPE RWD-2.0 RWD-2.5 RWD-3.0 RWD-4.0 RWD-5.0 RWD-6.0 NW(S)E- NW(S)E- NW(S)E- NW(S)E- NW(S)E- NW(S)E- Indoor unit model (200/260) (200/260) (200/260) (200/260) (200/260) (200/260) S(-K)
  • Seite 30 GENERAL DATA  YUTAKI S80 Outdoor unit model RAS-4WH(V)NPE RAS-5WH(V)NPE RAS-6WH(V)NPE Indoor unit model RWH-4.0(V)NF(W)E RWH-5.0(V)NF(W)E RWH-6.0(V)NF(W)E WIT / WOT Unit Heating operation (DB/WB) CAP (Nom./Max.) 11.0/15.2 14.0/16.7 16.0/17.8 30 / 35 ºC COP (Nom.) 5.00 4.71 4.57 CAP (Nom./Max.) 11.0/14.5 14.0/17.0 16.0/18.0...
  • Seite 31: Erp Performance Data

    GENERAL DATA 3.2 ERP PERFORMANCE DATA 3.2.1 General considerations • This appliance must be installed, maintained and dismantled by professionals. Do not pour contained refrigerant into the atmosphere since this refrigerant fluid is a fluorinated greenhouse gas regulated under European Regulation (EU) No 517/2014. •...
  • Seite 32 GENERAL DATA RAS-(4-6)WHVNPE + RWM-(4.0-6.0)NE Outdoor RAS-4WHVNPE RAS-5WHVNPE RAS-6WHVNPE unit Model Indoor unit RWM-4.0NE RWM-5.0NE RWM-6.0NE Water outlet temperature 35ºC 55ºC 35ºC 55ºC 35ºC 55ºC Air to water heat pump Heat pump combination heater Product description Low temperature heat pump Complementary heater Design capacity (P 11.0...
  • Seite 33 GENERAL DATA RAS-(4-6)WHNPE + RWM-(4.0-6.0)NE Outdoor unit RAS-4WHNPE RAS-5WHNPE RAS-6WHNPE Model Indoor unit RWM-4.0NE RWM-5.0NE RWM-6.0NE Water outlet temperature 35ºC 55ºC 35ºC 55ºC 35ºC 55ºC Air to water heat pump Heat pump combination heater Product description Low temperature heat pump Complementary heater Design capacity (P 11.0...
  • Seite 34 GENERAL DATA RAS-(8/10)WHNPE + RWM-(8.0/10.0)NE Outdoor unit RAS-8WHNPE RAS-10WHNPE Model Indoor unit RWM-8.0NE RWM-10.0NE Water outlet temperature 35ºC 55ºC 35ºC 55ºC Air to water heat pump Heat pump combination heater Product description Low temperature heat pump Complementary heater Design capacity (P 18.0 16.0 20.0...
  • Seite 35: Erp Data - Yutaki S Combi

    GENERAL DATA 3.2.2.2 ERP data - YUTAKI S COMBI  AVERAGE climate RAS-(2-3)WHVNP + RWD-(2.0-3.0)NW(S)E-(200/260)S(-K) Outdoor unit RAS-2WHVNP RAS-2.5WHVNP RAS-3WHVNP Model RWD-2.0NW(S)E- RWD-2.5NW(S)E- RWD-3.0NW(S)E- Indoor unit (200/260)S (200/260)S (200/260)S (-K) (-K) (-K) Water outlet temperature 35ºC 55ºC 35ºC 55ºC 35ºC 55º...
  • Seite 36 GENERAL DATA RAS-(4-6)WHVNPE + RWD-(4.0-6.0)NW(S)E-(200/260)S(-K) Outdoor unit RAS-4WHVNPE RAS-5WHVNPE RAS-6WHVNPE Model RWD-4.0NW(S)E- RWD-5.0NW(S)E- RWD-6.0NW(S)E- Indoor unit (200/260)S (200/260)S (200/260)S (-K) (-K) (-K) Water outlet temperature 35ºC 55ºC 35ºC 55ºC 35ºC 55º Air to water heat pump Heat pump combination heater Product description Low temperature heat pump...
  • Seite 37: Indoor Unit

    GENERAL DATA RAS-(4-6)WHNPE + RWD-(4.0-6.0)NW(S)E-(200/260)S(-K) Outdoor unit RAS-4WHNPE RAS-5WHNPE RAS-6WHNPE Model RWD-4.0NW(S)E- RWD-5.0NW(S)E- RWD-6.0NW(S)E- Indoor unit (200/260)S (200/260)S (200/260)S (-K) (-K) (-K) Water outlet temperature 35ºC 55ºC 35ºC 55ºC 35ºC 55º Air to water heat pump Heat pump combination heater Product description Low temperature heat pump...
  • Seite 38: Erp Data - Yutaki S80

    GENERAL DATA 3.2.2.3 ERP data - YUTAKI S80  AVERAGE climate RAS-(4-6)WHVNPE + RWH-(4.0-6.0)VNF(W)E Outdoor unit RAS-4WHVNPE RAS-5WHVNPE RAS-6WHVNPE Model Indoor unit RWH-4.0VNF(W)E RWH-5.0VNF(W)E RWH-6.0VNF(W)E Water outlet temperature 35ºC 55ºC 35ºC 55ºC 35ºC 55ºC Air to water heat pump Heat pump combination heater Product description Low temperature heat pump...
  • Seite 39 GENERAL DATA RAS-(4-6)WHNPE + RWH-(4.0-6.0)NF(W)E Outdoor unit RAS-4WHNPE RAS-5WHNPE RAS-6WHNPE Model Indoor unit RWH-4.0NF(W)E RWH-5.0NF(W)E RWH-6.0NF(W)E Water outlet temperature 35ºC 55ºC 35ºC 55ºC 35ºC 55ºC Air to water heat pump Heat pump combination heater Product description Low temperature heat pump Complementary heater Design capacity (P 11.0...
  • Seite 40: Erp Data - Yutaki M

    GENERAL DATA 3.2.2.4 ERP data - YUTAKI M  AVERAGE climate RASM-(3-6)VNE Model RASM-3VNE RASM-4VNE RASM-5VNE RASM-6VNE Water outlet temperature 35ºC 55ºC 35ºC 55ºC 35ºC 55ºC 35ºC 55ºC Air to water heat pump Heat pump combination Product heater description Low temperature heat pump Complementary heater Design capacity (P 11.0...
  • Seite 41 GENERAL DATA RASM-(4-6)NE Model RASM-4NE RASM-5NE RASM-6NE Water outlet temperature 35ºC 55ºC 35ºC 55ºC 35ºC 55ºC Air to water heat pump Heat pump combination heater Product description Low temperature heat pump Complementary heater Design capacity (P 11.0 10.0 14.0 12.0 16.0 14.0 DESIGN...
  • Seite 42: Erp Additional Data - Yutaki S

    GENERAL DATA 3.2.2.5 ERP additional data - YUTAKI S RAS-(2-3)WHVNP + RWM-(2.0-3.0)NE Outdoor unit RAS-2WHVNP RAS-2.5WHVNP RAS-3WHVNP Model Indoor unit RWM-2.0NE RWM-2.5NE RWM-3.0NE Electrical power input in stand-by mode (Psb) 11.9 11.9 11.9 Electrical power input in thermostat-OFF mode (Pto) Electrical power input in OFF mode (Poff) 11.9 11.9...
  • Seite 43: Erp Additional Data - Yutaki S Combi

    GENERAL DATA 3.2.2.6 ERP additional data - YUTAKI S COMBI RAS-(2-3)WHVNP + RWD-(2.0-3.0)NW(S)E-(200/260)S(-K) Outdoor unit RAS-2WHVNP RAS-2.5WHVNP RAS-3WHVNP Model RWD-2.0NW(S)E RWD-2.5NW(S)E RWD-3.0NW(S)E Indoor unit (200/260)S(-K) (200/260)S(-K) (200/260)S(-K) Electrical power input in stand-by mode (Psb) 11.9 11.9 11.9 Electrical power input in thermostat-OFF mode (Pto) Electrical power input in OFF mode (Poff) 11.9 11.9...
  • Seite 44: Erp Additional Data - Yutaki S80

    GENERAL DATA 3.2.2.7 ERP additional data - YUTAKI S80 RAS-(4-6)WHVNPE + RWH-(4.0-6.0)VNF(W)E Outdoor unit RAS-4WH(V)NPE RAS-5WH(V)NPE RAS-6WH(V)NPE Model Indoor unit RWH-4.0VNF(W)E RWH-5.0VNF(W)E RWH-6.0VNF(W)E Electrical power input in stand-by mode (Psb) 17.0 17.0 17.0 Electrical power input in thermostat-OFF mode (Pto) Electrical power input in OFF mode (Poff) 17.0 17.0...
  • Seite 45: General Specifications

    GENERAL DATA 3.3 GENERAL SPECIFICATIONS 3.3.1 Considerations • The sound data is based on the following conditions: Outdoor ambient temperature (DB/WB): 7/6ºC. Water inlet/outlet temperature: 47/55ºC (mark: *1); 30/35ºC (mark: *2). Distance of the unit from the measuring point: At 1 meter from the unit’s front surface; 1,5 meter from floor level. The sound pressure level is measured in an anechoic chamber, so reflected sound should be taken into consideration when installing the unit.
  • Seite 46 GENERAL DATA Model RAS-4WHVNPE RAS-5WHVNPE RAS-6WHVNPE Power supply 1~ 230V 50Hz Noise level (sound pressure) (*1) dB(A) (*1) dB(A) Noise level (sound power) (*2) dB(A) Air flow /min Cabinet colour Natural grey (1.0Y 8.5/0.5) Dimensions (H x W x D) 1380 x 950 x 370 Net weight Gross weight...
  • Seite 47 GENERAL DATA Model RAS-8WHNPE RAS-10WHNPE Power supply 3N~ 400V 50Hz Noise level (sound pressure) (*1) dB(A) (*1) dB(A) Noise level (sound power) (*2) dB(A) Air flow /min Cabinet colour Natural grey (1.0Y 8.5/0.5) Dimensions (H x W x D) 1380 x 950 x 370 Net weight Gross weight Piping diameter (liquid / gas)
  • Seite 48: Split System - Indoor Unit

    GENERAL DATA 3.3.3 Split system - Indoor unit 3.3.3.1 YUTAKI S Model RWM-2.0NE RWM-2.5NE RWM-3.0NE Power supply 1~ 230V 50Hz Noise level (sound power) dB(A) Material Precoated galvanised steel Cabinet Colour Pure white (RAL 9010) Height (with connections) 712 (782) Unit dimensions Width Depth...
  • Seite 49 GENERAL DATA Model RWM-4.0NE RWM-5.0NE RWM-6.0NE Power supply 1~ 230V 50Hz / 3N~ 400V 50Hz Noise level (sound power) dB(A) Material Precoated galvanised steel Cabinet Colour Pure white (RAL 9010) Height (with connections) 890 (960) Unit dimensions Width Depth Height Packaging Width 1120...
  • Seite 50 GENERAL DATA Model RWM-8.0NE RWM-10.0NE Power supply 3N~ 400V 50Hz Noise level (sound power) dB(A) Material Precoated galvanised steel Cabinet Colour Pure white (RAL 9010) Height (with connections) 890 (960) Unit dimensions Width Depth Height Packaging Width 1120 dimensions Depth Packaging volume m³...
  • Seite 51: Yutaki S Combi

    GENERAL DATA 3.3.3.2 YUTAKI S COMBI  Standard model RWD-2.0NWE- RWD-2.5NWE- RWD-3.0NWE- Model (200/260)S (200/260)S (200/260)S Power supply 1~ 230V 50Hz Noise level (sound power) dB(A) Material Precoated galvanised steel Cabinet Colour Pure white (RAL 9010) Height (with connections) 1750 (1816) (*3) Unit dimensions Width Depth...
  • Seite 52 GENERAL DATA RWD-4.0NWE- RWD-5.0NWE- RWD-6.0NWE- Model (200/260)S (200/260)S (200/260)S Power supply 1~ 230V 50Hz / 3N~ 400V 50Hz Noise level (sound power) dB(A) Material Precoated galvanised steel Cabinet Colour Pure white (RAL 9010) Height (with connections) 1750 (1816) (*3) Unit dimensions Width Depth Height...
  • Seite 53 GENERAL DATA  Model for solar combination Model RWD-2.0NWSE-260S RWD-2.5NWSE-260S RWD-3.0NWSE-260S Power supply 1~ 230V 50Hz Noise level (sound power) dB(A) Material Precoated galvanised steel Cabinet Colour Pure white (RAL 9010) Height (with connections) 1750 (1816) (*3) Unit dimensions Width Depth Height Packaging dimensions...
  • Seite 54 GENERAL DATA Model RWD-4.0NWSE-260S RWD-5.0NWSE-260S RWD-6.0NWSE-260S Power supply 1~ 230V 50Hz / 3N~ 400V 50Hz Noise level (sound power) Material Precoated galvanised steel Cabinet Colour Pure white (RAL 9010) Height (with connections) 1750 (1816) (*3) Unit dimensions Width Depth Height 1950 Packaging dimensions Width...
  • Seite 55 GENERAL DATA  Model for UK market RWD-2.0NWE- RWD-2.5NWE- RWD-3.0NWE- Model (200/260)S-K (200/260)S-K (200/260)S-K Power supply 1~ 230V 50Hz Noise level (sound power) dB(A) Material Precoated galvanised steel Cabinet Colour Pure white (RAL 9010) Height (with connections) 1750 (1816) (*3) Unit dimensions Width Depth...
  • Seite 56 GENERAL DATA RWD-4.0NWE- RWD-5.0NWE- RWD-6.0NWE- Model (200/260)S-K (200/260)S-K (200/260)S-K Power supply 1~ 230V 50Hz / 3N~ 400V 50Hz Noise level (sound power) dB(A) Material Precoated galvanised steel Cabinet Colour Pure white (RAL 9010) Height (with connections) 1750 (1816) (*3) Unit dimensions Width Depth Height...
  • Seite 57: Yutaki S80

    GENERAL DATA 3.3.3.3 YUTAKI S80  Indoor unit Version for indoor unit alone Model RWH-4.0(V)NFE RWH-5.0(V)NFE RWH-6.0(V)NFE RWH-(4.0-6.0)VNFWE: 1~ 230V 50Hz Power supply RWH-(4.0-6.0)NFWE: 3N~ 400V 50Hz Noise level (sound power) dB(A) Material Precoated galvanised steel Cabinet Colour Pure white (RAL 9010) Height (with connections) (*) 751 (802) (*3) Unit dimensions...
  • Seite 58 GENERAL DATA Version for combination with DHW tank Model RWH-4.0(V)NFWE RWH-5.0(V)NFWE RWH-6.0(V)NFWE RWH-(4.0-6.0)VNFWE: 1~ 230V 50Hz Power supply RWH-(4.0-6.0)NFWE: 3N~ 400V 50Hz Noise level (sound power) dB(A) Material Precoated galvanised steel Cabinet Colour Pure white (RAL 9010) Height 751 (*3) Unit dimensions Width Depth (with connections)
  • Seite 59 GENERAL DATA  Domestic hot water tank Model DHWS200S-2.7H2E DHWS260S-2.7H2E Power supply 1~ 230V 50Hz Material Precoated galvanised steel Cabinet Colour Pure white (RAL 9010) Separated tank 1282 (*3) 1591 (*3) Height Integrated tank 1980 (*3) 2289 (*3) Unit dimensions Width Depth (with connections) 648 (675)
  • Seite 60: Monobloc System - Yutaki M

    GENERAL DATA 3.3.4 Monobloc system - YUTAKI M Model RASM-3VNE RASM-4VNE RASM-5VNE RASM-6VNE Power supply 1~ 230V 50Hz Noise level (sound pressure) (*1)(*2) dB(A) (*1) dB(A) Noise level (sound power) (*2) dB(A) Material Precoated galvanised steel Cabinet Colour Natural grey (1.0Y 8.5/0.5) Height 1380 Unit dimensions...
  • Seite 61 GENERAL DATA Model RASM-4NE RASM-5NE RASM-6NE Power supply 3N~ 400V 50Hz Noise level (sound pressure) (*1)(*2) dB(A) Noise level (sound power) (*1)(*2) dB(A) Material Precoated galvanised steel Cabinet Colour Natural grey (1.0Y 8.5/0.5) Height 1380 Unit dimensions Width 1252 Depth Height 1515 Packaging dimensions...
  • Seite 62: Component Data

    GENERAL DATA 3.4 COMPONENT DATA 3.4.1 Split system - Outdoor unit MODEL RAS-2WHVNP RAS-2.5WHVNP RAS-3WHVNP Type Multi-pass cross-finned tube Pipe material Copper Outer diameter Rows Number of tubes in the heat exchanger Air heat exchanger Fin material Aluminium Fin pitch 1.45 Maximum operating pressure 4.15...
  • Seite 63 GENERAL DATA MODEL RAS-8WHNPE RAS-10WHNPE Type Multi-pass cross-finned tube Pipe material Copper Outer diameter Rows Number of tubes in the heat exchanger Air heat exchanger Fin material Aluminium Fin pitch Maximum Heat exchanger pressure 4.15 Total front area 1.35 Number of evaporators per unit Fan type Direct drive propeller fan Fans per unit...
  • Seite 64: Split System - Indoor Unit

    GENERAL DATA 3.4.2 Split system - Indoor unit 3.4.2.1 YUTAKI S RWM-2.0 RWM-2.5 RWM-3.0 RWM-4.0 RWM-5.0 RWM-6.0 RWM-8.0 RWM-10.0 Model Type Brazed plate Material Stainless steel Transfer fluids R410A - H Quantity Internal refrigerant volume 0.54 0.73 0.81 1.55 2.09 2.09 3.19 3.91...
  • Seite 65: Yutaki S Combi

    GENERAL DATA 3.4.2.2 YUTAKI S COMBI  Standard model and UK market model RWD-2.0NWE- RWD-2.5NWE- RWD-3.0NWE- RWD-4.0NWE- RWD-5.0NWE- RWD-6.0NWE- Model (200/260)S(-K) (200/260)S(-K) (200/260)S(-K) (200/260)S(-K) (200/260)S(-K) (200/260)S(-K) Casing material Stainless steel RWD-NWE-200S(-K): 200 L Nominal water volume RWD-NWE-260S(-K): 260 L RWD-NWE-200S(-K): 190L Net water volume RWD-NWE-260S(-K): 250L Material...
  • Seite 66 GENERAL DATA RWD-2.0NWE- RWD-2.5NWE- RWD-3.0NWE- RWD-4.0NWE- RWD-5.0NWE- RWD-6.0NWE- Model (200/260)S(-K) (200/260)S(-K) (200/260)S(-K) (200/260)S(-K) (200/260)S(-K) (200/260)S(-K) Material Steel (with stainless/galvanized steel connections) Internal water volume Working pressure Pre-loading pressure (Air side) Type Isolated water strainer (Filter ball) Material Brass Piping connection (in) 1”, DN25 1”, DN32...
  • Seite 67 GENERAL DATA  Model for solar combination RWD-2.0 RWD-2.5 RWD-3.0 RWD-4.0 RWD-5.0 RWD-6.0 NW(S)E- NW(S)E- NW(S)E- NW(S)E- NW(S)E- NW(S)E- Model 260S 260S 260S 260S 260S 260S Casing material Stainless steel RWD-NWE-200S: 200 L Nominal water volume RWD-NWE-260S: 260 L RWD-NWE-200S: 190L Net water volume RWD-NWE-260S: 250L Material...
  • Seite 68 GENERAL DATA RWD-2.0 RWD-2.5 RWD-3.0 RWD-4.0 RWD-5.0 RWD-6.0 Model NW(S)E- NW(S)E- NW(S)E- NW(S)E- NW(S)E- NW(S)E- 260S 260S 260S 260S 260S 260S Material Steel (with stainless/galvanized steel connections) Internal water volume Working pressure Pre-loading pressure (Air side) Type Isolated water strainer (Filter ball) Material Brass Piping connection...
  • Seite 69: Yutaki S80

    GENERAL DATA 3.4.2.3 YUTAKI S80 Model RWH-4.0(V)NF(W)E RWH-5.0(V)NF(W)E RWH-6.0(V)NF(W)E 1~ 230V 50Hz H405DHD-64A1 H405DHD-64A1 H405DHD-64A1 Model 3N~ 400V 50Hz H405DHD-64D1 H405DHD-64D1 H405DHD-64D1 Type Scroll DC Inverter driven Discharge 2.94 Pressure resistance Suction 0.15 Starting method Inverter-driven (I.D.) Motor type Poles Insulation class Oil type FVC68D...
  • Seite 70: Dhw Tank

    GENERAL DATA 3.4.2.4 DHW tank Model DHWS200S-2.7H2E DHWS260S-2.7H2E Power supply 1~230V 50Hz Material Precoated galvanised steel Casing Color Pure white (RAL 9010) Separated tank 1282(*3) 1591(*3) Height Integrated tank 1980(*3) 2289(*3) Unit Width Depth (with connections) 648 (675) Dimensions Height 1444 1753 Width...
  • Seite 71 GENERAL DATA Monobloc system - YUTAKI M Model RASM-3VNE RASM-4(V)NE RASM-5(V)NE RASM-6(V)NE 1~ 230V 50Hz 2YC45KXD E402HHD-36A2 Model 3N~ 400V 50Hz E402HHD-36D2 Type Scroll DC Inverter driven Discharge 4.15 Pressure resistance Suction 2.21 Starting method Direct current control Motor type Poles Insulation class Oil type...
  • Seite 72 GENERAL DATA Model RASM-3VNE RASM-4(V)NE RASM-5(V)NE RASM-6(V)NE Material Stainless steel (Immersion heating element) Internal water volume Working pressure Pre-loading pressure (Air side) Type Isolated water strainer (Filter ball) Material Brass Piping connection (in) 1”, DN25 Mesh (hole size) Automatic filter cleaning Safety valve Yes (3 bar) Shut-off valve...
  • Seite 73: Electrical Data

    The power supply cables must be sized to cover this maximum current value. • Specifications in these tables are subject to change without notice in order that HITACHI may bring the latest innovations to their customers. • Please refer to the general information, cautions and notes regarding protective devices (CB, ELB) throughout the “7.
  • Seite 74: Split System - Indoor Unit

    GENERAL DATA 3.5.3 Split system - Indoor unit 3.5.3.1 YUTAKI S RWM-(2.0-10.0)NE Applicable voltage Max. Model Power supply Operation mode U max. U min. (kW) (kW) 0.05 0.05 Without electric heater With electric heater 13.2 3.05 14.5 3.05 RWM-(2.0-3.0)NE 1~ 230V 50Hz 13.2 3.05 14.5...
  • Seite 75: Yutaki S80

    GENERAL DATA 3.5.3.3 YUTAKI S80  Version for indoor unit alone RWH-(4.0-6.0)(V)NFE Applicable voltage Max. Model Power supply Operation mode U max. U min. (kW) (kW) 12.1 2.73 5.33 Without DHW tank heater RWH-4.0VNFE 25.4 5.73 8.33 With DHW tank heater 12.3 2.78 6.23...
  • Seite 76: Monobloc System - Yutaki M

    GENERAL DATA 3.5.4 Monobloc system - YUTAKI M RASM-(3-6)(V)NE Applicable voltage Compressor and fan motors Max. Model Power supply Operation mode U max. U min. (kW) (KW) Without DHW tank heater 1.93 18.0 4.09 RASM-3VNE With DHW tank heater 21.5 4.93 33.0 7.56...
  • Seite 77: Working Range

    WORKING RANGE 4 WORKING RANGE 4.1 POWER SUPPLY WORKING RANGE  Nominal power supply • Single phase: 1~ 230V 50Hz • Three phase: 3N~ 400V 50Hz  Operating voltage Between 90 and 110% of the nominal voltage.  Voltage imbalance for nominal power supply 3N~ 400V 50Hz Up to 3% of each phase, measured at the main terminal of the outdoor unit.
  • Seite 78 WORKING RANGE  YUTAKI M Water outlet temperature (Cº) (*): Limit for 3HP Continuous working range. Outdoor unit operation is possible, but the capacity is not guaranteed. Indoor unit and back-up heater are operating. Only back-up heater. (No outdoor unit operation). Ambient temperature (ºC(DB)) ...
  • Seite 79: Dhw

    N O T E The heat pump can produce domestic hot water at 57ºC as a maximum (53ºC for 2.0/2.5/3.0HP) by itself, but HITACHI recommends to set the temperature of the tank by heat pump only up to 55ºC (50ºC for 2.0/2.5/3.0HP) and keep Thpoff default value. In case of higher setting, the tank’s heater must be used to reach the setting temperature (enabled by optional function).
  • Seite 80: Swimming Pool Heating

    WORKING RANGE  For YUTAKI S80 DHW water temperature (ºC) Continuous working range. Outdoor unit operation is possible, but the capacity is not guaranteed. Indoor unit and back-up heater are operating. Ambient temperature Only back-up heater. (No outdoor unit operation). (ºC(DB)) (*): Limit for 3HP 4.2.3 Swimming pool heating...
  • Seite 81: Hydraulic Working Range

    WORKING RANGE 4.3 HYDRAULIC WORKING RANGE 4.3.1 Hydraulic data  YUTAKI S MODEL 2.0 HP 2.5 HP 3.0 HP 4.0 HP 5.0 HP 6.0 HP 8.0 HP 10.0 HP Minimum water flow rate (*1) Maximum water flow rate (*1) Minimum installation water volume (*2) Minimum allowable water pressure Maximum allowable water pressure ...
  • Seite 82: Pump Performance Curves

    WORKING RANGE 4.3.2 Pump performance curves N O T E If a water flow rate is selected out of the working range of the unit, it can cause malfunction on the unit. Please, try to operate the pump within the minimum and maximum water flow of the indoor unit.
  • Seite 83 WORKING RANGE 5.0 HP 6.0 HP Water flow (m Water flow (m 8.0 HP 10.0 HP Water flow (m Water flow (m PMML0335A rev.1 - 04/2016...
  • Seite 84 WORKING RANGE  YUTAKI S COMBI 2.0 HP 2.5 HP Water flow (m Water flow (m 3.0 HP 4.0 HP Water flow (m Water flow (m 5.0 HP 6.0 HP Water flow (m Water flow (m PMML0335A rev.1 - 04/2016...
  • Seite 85 WORKING RANGE  YUTAKI S80 Version for indoor unit alone 4.0 HP 5.0 HP Water flow (m Water flow (m 6.0 HP Water flow (m PMML0335A rev.1 - 04/2016...
  • Seite 86 WORKING RANGE Version for combination with DHW tank 4.0 HP 5.0 HP Water flow (m Water flow (m 6.0 HP Water flow (m PMML0335A rev.1 - 04/2016...
  • Seite 87 WORKING RANGE  YUTAKI M 3.0 HP 4.0 HP Water flow (m Water flow (m 5.0 HP 6.0 HP Water flow (m Water flow (m PMML0335A rev.1 - 04/2016...
  • Seite 88: Refrigerant Cycle And Hydraulic Circuit

    REFRIGERANT CYCLE AND HYDRAULIC CIRCUIT 5 REFRIGERANT CYCLE AND HYDRAULIC CIRCUIT 5.1 REFRIGERANT CYCLE AND HYDRAULIC CIRCUIT FOR SPLIT SYSTEM 5.1.1 YUTAKI S  RAS-(2-3)WHVNP + RWM-(2.0-3.0)NE PMML0335A rev.1 - 04/2016...
  • Seite 89 REFRIGERANT CYCLE AND HYDRAULIC CIRCUIT  RAS-(4-6)WH(V)NPE + RWM-(4.0-6.0)NE PMML0335A rev.1 - 04/2016...
  • Seite 90 REFRIGERANT CYCLE AND HYDRAULIC CIRCUIT  RAS-(8/10)WHNPE + RWM-(8.0-10.0)NE PMML0335A rev.1 - 04/2016...
  • Seite 91: Yutaki S Combi

    REFRIGERANT CYCLE AND HYDRAULIC CIRCUIT 5.1.2 YUTAKI S COMBI  RAS-(2-3)WHVNP + RWD-(2.0-3.0)NW(S)E-(200/260)S(-K) PMML0335A rev.1 - 04/2016...
  • Seite 92 REFRIGERANT CYCLE AND HYDRAULIC CIRCUIT  RAS-(4-6)WHVNP + RWD-(4.0-6.0)NW(S)E-(200/260)S(-K) PMML0335A rev.1 - 04/2016...
  • Seite 93: Yutaki S80

    REFRIGERANT CYCLE AND HYDRAULIC CIRCUIT 5.1.3 YUTAKI S80 5.1.3.1 Indoor unit standalone version  RAS-(4-6)WHVNP + RWH-(4.0-6.0)(V)NFE PMML0335A rev.1 - 04/2016...
  • Seite 94: Indoor Unit For Integrated Tank Version

    REFRIGERANT CYCLE AND HYDRAULIC CIRCUIT 5.1.3.2 Indoor unit for integrated tank version  RAS-(4-6)WHVNP + RWH-(4.0-6.0)(V)NFWE PMML0335A rev.1 - 04/2016...
  • Seite 95: Refrigerant Cycle And Hydraulic Circuit For Monobloc System - Yutaki M

    REFRIGERANT CYCLE AND HYDRAULIC CIRCUIT 5.2 REFRIGERANT CYCLE AND HYDRAULIC CIRCUIT FOR MONOBLOC SYSTEM - YUTAKI M  RAS-3WHVNE PMML0335A rev.1 - 04/2016...
  • Seite 96 REFRIGERANT CYCLE AND HYDRAULIC CIRCUIT  RAS-(4-6)WH(V)NE PMML0335A rev.1 - 04/2016...
  • Seite 97: Refrigerant And Water Piping

    REFRIGERANT AND WATER PIPING 6 REFRIGERANT AND WATER PIPING 6.1 REFRIGERANT CIRCUIT 6.1.1 Refrigerant piping  Refrigerant piping length between indoor unit and outdoor unit (For YUTAKI (S/S COMBI/S80)) The refrigerant piping length between indoor unit and outdoor unit should be designed using the following chart. Keep the design point within the area of the chart, which is showing the applicable height difference according to piping length.
  • Seite 98: Precautions In The Event Of Gas Refrigerant Leaks

    REFRIGERANT AND WATER PIPING 6.1.2 Precautions in the event of gas refrigerant leaks The installers and those responsible for drafting the specifications are obliged to comply with local safety codes and regulations in the case of refrigerant leakage. C A U T I O N •...
  • Seite 99: Water Piping

    REFRIGERANT AND WATER PIPING  Countermeasure in the event of possible refrigerant leakage The room must have the following features to prevent suffocation in case a refrigerant leakage occurs: 1 Provide a shutterless opening which will allow fresh air to circulate into the room. 2 Provide a doorless opening of 0.15% or more size to the floor area.
  • Seite 100 G 1-1/4” G 1-1/4” G 1-1/4” (male) - (4.0-6.0)HP (female) (female) G 1-1/4” (male) Type 2: Version for operation with an HITACHI DHW tank (RWH-(4.0-6.0)(V)NFWE) (inches) Space heating connection Heating coil connection Model Inlet Outlet Inlet connection Outlet connection...
  • Seite 101 For DHW tank beside the indoor unit (both right or left side), the heating coil pipes factory-supplied with the DHW tank accessory are not required. In this case, the dedicated HITACHI flexible water pipe kit (ATW-FWP-02 accessory) is needed. This kit is provided...
  • Seite 102: Water Quality (Preliminary Information)

    REFRIGERANT AND WATER PIPING Heating coil pipes for the indoor unit Item Connection ~500 mm To connect to the 3-way valve heating coil inlet connection. ~400 mm To connect to the T-branch heating coil outlet connection. Heating coil pipes for the DHW tank accessory Item Connection One pipe to connect to the heating coil inlet connection of the tank...
  • Seite 103: Electrical And Control Settings

    ELECTRICAL AND CONTROL SETTINGS 7 ELECTRICAL AND CONTROL SETTINGS 7.1 GENERAL CHECK • Make sure that the following conditions related to power supply installation are satisfied: The power capacity of the electrical installation is large enough to support the power demand of the YUTAKI system (outdoor unit + indoor unit + DHW tank (if apply)).
  • Seite 104: Indoor Unit In Combination With Dhw Tank

    ELECTRICAL AND CONTROL SETTINGS YUTAKI S COMBI Model Power supply Operation mode (Ω) Without electric heaters With electric heater RWD-(2.0-3.0) 1~ 230V 50Hz NW(S)E-(200/260)S With DHW tank heater With electric and DHW tank heaters 0.28 Without electric heaters With electric heater 0.26 1~ 230V 50Hz With DHW tank heater...
  • Seite 105 ELECTRICAL AND CONTROL SETTINGS  Monobloc system - YUTAKI M Model Power supply Operation mode (Ω) Without DHW tank heater 0.35 RASM-3VNE With DHW tank heater 0.22 Without DHW tank heater 0.24 RASM-4VNE With DHW tank heater 0.17 1~ 230V 50Hz Without DHW tank heater 0.24 RASM-5VNE...
  • Seite 106: Electrical Connection

    ELECTRICAL AND CONTROL SETTINGS 7.2 ELECTRICAL CONNECTION C A U T I O N • Check to ensure that the field supplied electrical components (mains power switches, circuit breakers, wires, connectors and wire terminals) have been properly selected according to the electrical data indicated on this chapter and they comply with national and local codes. If it is necessary, contact with your local authority in regards to standards, rules, regulations, etc.
  • Seite 107 ELECTRICAL AND CONTROL SETTINGS YUTAKI S COMBI Power supply Transmitting Actuator Max. cables cables cables Model Power supply Operation mode current EN60335-1 EN60335-1 EN60335-1 2 x 0.75 mm² + GND Without electric heaters 2 x 2.5 mm² + GND With electric heater RWD-(2.0-3.0) 1~230V 50Hz NW(S)E-(200/260)S(-K)
  • Seite 108: Minimum Requirements Of The Protection Devices

    ELECTRICAL AND CONTROL SETTINGS  Monobloc system - YUTAKI M Power supply Transmitting Actuator Max. cables cables cables Power supply Operation mode Model current EN60335-1 EN60335-1 EN60335-1 2 x 6.0 mm² + GND Without DHW tank heater RASM-3VNE With DHW tank heater 2 x 10.0 mm²...
  • Seite 109 ELECTRICAL AND CONTROL SETTINGS  Split system - Indoor unit YUTAKI S Applicable voltage Model Power supply Operation mode U max. U min. (nº of poles/A/mA) Without electric heaters With electric heater RWM-(2.0-3.0)NE 1~ 230V 50Hz 2/40/30 With DHW tank heater With electric and DHW tank heaters Without electric heaters With electric heater...
  • Seite 110 ELECTRICAL AND CONTROL SETTINGS YUTAKI S80 Version for indoor unit alone Applicable voltage Model Power supply Operation mode (nº of poles/A/mA) U max. (V) U min. (V) Without DHW tank heater RWH-4.0VNFE With DHW tank heater 2/40/30 Without DHW tank heater RWH-5.0VNFE 1~ 230V 50Hz With DHW tank heater...
  • Seite 111: Setting Of Dip Switches And Rsw Switches

    ELECTRICAL AND CONTROL SETTINGS 7.3 SETTING OF DIP SWITCHES AND RSW SWITCHES 7.3.1 Outdoor unit 7.3.1.1 Location of DIP switches and rotary switches The PCB in the outdoor unit is operating with DIP switches and push switches. The location is as follows: RAS-(2/2.5)WHVNP PCB1 RAS-(3-10)WH(V)NPE...
  • Seite 112: Function Of Dip Switches And Rotary Switches

    ELECTRICAL AND CONTROL SETTINGS 7.3.1.2 Function of DIP switches and rotary switches N O T E • The mark “■” indicates the position of dips switches. • No mark “■” indicates pin position is not affecting. • The figures show the settings before shipment or after selection. D A N G E R Before setting dips switches, first turn the power source off and then set the position of the dips switches.
  • Seite 113 ELECTRICAL AND CONTROL SETTINGS  DSW2: Piping length/selection function Setting before shipment Control to support existing pipes. When using Ø19,05 gas pipe (soft-annealed), switch ON DSW2 pin 4 in the outdoor unit PCB) Optional function setting mode (The optional function selection mode becomes available) External input/output setting mode (The input / output signals selection mode becomes available).
  • Seite 114: Led Indication

    ELECTRICAL AND CONTROL SETTINGS 7.3.1.3 LED indication LED Indication LED1 This LED indicates the transmission status between the indoor unit and the unit controller LED2 Yellow This LED indicates the transmission status between the indoor unit and the outdoor unit LED3 Green Power source for the PCB...
  • Seite 115: Terminal Board Connections

    ELECTRICAL AND CONTROL SETTINGS 7.4 TERMINAL BOARD CONNECTIONS 7.4.1 Table board 1  Main power supply The main power supply connection is wired to the Terminal board (TB1) as follows: Outdoor unit Outdoor unit Operating Line Operating Line RAS-WHVNP(E) RAS-WHNPE (Twisted shielded pair cable or shielded pair cable) (Twisted shielded DC5V (Non-Pole Transmission, H-LINK system)
  • Seite 116: Table Board 2

    ELECTRICAL AND CONTROL SETTINGS 7.4.2 Table board 2 Input and output terminals give the possibility to configure the installation according to the needs of the user. The default settings and I/O terminals reach most of the options necessary for an optimal performance of the system. Additionally, the settings can be modified through the unit controller, and input/output terminals can be used, if required, to have additional options.
  • Seite 117 ELECTRICAL AND CONTROL SETTINGS Input terminals (Optional input functions) Additionally to the factory-set functions, YUTAKI series allow to other configurations depending on the needs of the customer. All those inputs are configurable from the “I/O and sensor“ menu of Unit controller are the following: Inputs: Demand ON/OFF, Smart act., Swimming pool input, Solar, Operation mode, DHW boost, Power Meter 1, Demand ON/OFF C1, Demand ON/FF C2, Forced heating, Forced cooling, Power meter 2, ECO mode C1 and C2, ECO mode C1, ECO mode C2, Forced OFF, SG 2.
  • Seite 118 ELECTRICAL AND CONTROL SETTINGS b. Installation of the ATW-RTU-04 In case of setting an installation with 2 circuits (circuit 1 and circuit 2) and the same demand ON/OFF is used for both of them, remove the jumper between terminals 13 and 14 of the Terminal board 2 and connect the RF receiver as shown in the following picture.
  • Seite 119 ELECTRICAL AND CONTROL SETTINGS  Smart tariff (input 5) This function can be used to block or limit the heat pump. It allows an external Smart switch device to switch off or limit the heat pump during a period of peak electricity demand. Terminals 16 and 19 of the TB2. Common Line Smart F.
  • Seite 120 Spring return 2-wire type 3-way valve: the 3-way valve should be fitted when normally working (not power to the valve). Normally diverts to heating circuit side. • When using SPST 3-wire valve, HITACHI is not responsible for its operation. PMML0335A rev.1 - 04/2016...
  • Seite 121 Spring return 2-wire type 3-way valve: the 3-way valve should be fitted when normally working (not power to the valve). Normally diverts to heating circuit side. • When using SPST 3-wire valve, HITACHI is not responsible for its operation.  Water pump 3 (Output 2)
  • Seite 122: Unit Controller

    UNIT CONTROLLER 8 UNIT CONTROLLER The new unit controller for YUTAKI series (PC-ARFHE) is an user-friendly remote control which ensures a strong and safe communication through H-LINK. 8.1 DEFINITION OF THE SWITCHES        Liquid Crystal Display ...
  • Seite 123: Description Of The Icons

    UNIT CONTROLLER 8.2 DESCRIPTION OF THE ICONS 8.2.1 Common icons Icon Name Values Explanation Circuit I or II is in Demand-OFF Circuit I or II is on Thermo-OFF Status for circuit 1, 2, Circuit I or II is working between 0 < X ≤ 33% of the desired water outlet DHW and swimming temperature pool.
  • Seite 124: Icons For The Comprehensive View

    UNIT CONTROLLER 8.2.2 Icons for the comprehensive view Icon Name Values Explanation This icon informs about pump operation. Pump There are three available pumps on the system. Each one is numbered, and its corresponding number is displayed below to the pump icon when it is operating Heater step Indicates which of the 3 possible heater steps is applied on space heating DHW Heater...
  • Seite 125: Icons For The Room Thermostat View

    UNIT CONTROLLER 8.2.3 Icons for the room thermostat view Icon Name Values Explanation Manual mode Manual/Auto mode Auto mode with timer setting Auto mode without timer setting Setting temperature Setting/Room temperature Room temperature End of timer period The end hour of the timer period is indicated below this icon End of holiday period The end hour of the holiday period is indicated below this icon This icon appears while the setting temperature is being changed, and indicates the actual...
  • Seite 126: Contents

    UNIT CONTROLLER 8.3 CONTENTS Menu Contents Menu Contents Level 1 Level 2 Level 3 Level 4 Level 5 Level 6 Level 1 Level 2 Level 3 Level 4 Level 5 Level 6 Operation Information Timer Type General Simple Circuit 1 Schedule Swimming Pool Circuit 2...
  • Seite 127: Contents

    UNIT CONTROLLER Menu Contents Menu Contents Level 1 Level 2 Level 3 Level 4 Level 5 Level 6 Level 1 Level 2 Level 3 Level 4 Level 5 Level 6 Controller Settings Water Pump Configuration Controller Options Outdoor average Timer Room Name Minimum ON Time Date and Time...
  • Seite 128: Main Screen

    UNIT CONTROLLER 8.4 MAIN SCREEN Depending on the working mode of the user controller, the main screen is shown in a different way. When the user controller is working as a master unit controller, a comprehensive view with all the elements is shown, whereas when the user controller is working as a room thermostat (located in one of the controlled zones), the main screen appears with simplified information.
  • Seite 129: Room Thermostat View

    UNIT CONTROLLER 8.4.2 Room thermostat view             Time and date Next operation The current time/date information is displayed. This In this area, the end hour of the simple timer or holiday or information can be changed on the configuration menu next schedule action is indicated below its respective icon.
  • Seite 130: Wizard Start-Up Configuration

    UNIT CONTROLLER 8.5 WIZARD START-UP CONFIGURATION Once the design and installation of the system has been carried out, please set the controller following the wizard indication. After starting-up the system for the first time, the controller remains in a “Connecting” state, waiting for the indoor unit to send the following parameters: •...
  • Seite 131: Configuration Assistant

    UNIT CONTROLLER 8.5.1 Configuration Assistant 8.5.1.1 General overview Indoor unit Is this device attached to the unit? Indoor unit Is this device controlling the unit? PC-ARFHE as Is this device used as a Room MASTER Thermostat of a zone? YES, Is this device used as a Room YES, in YES, in...
  • Seite 132: Questions

    UNIT CONTROLLER 8.5.1.2 Questions In case of executing the Configuration Assistant, each line is a screen with a question: Questions Description Default Value Range Steps Units Application Notes Controller Configuration SC S80 When the device is installed in a different site than the unit. Is this device attached If “Yes”...
  • Seite 133 UNIT CONTROLLER Questions Description Default Value Range Steps Units Application Notes Controller Configuration SC S80 If question 3 has been answered with a different answer than “No”, Configuration Assistant task will have finished after this question, since the room How many thermostats have to be Question 11 thermostats are...
  • Seite 134: Results

    UNIT CONTROLLER 8.5.1.3 Results Question Description Answers Action Question 1 Is this device attached to the unit? It jumps to the question3 and selects automatically “Yes” for the question 2. Question 2 Is this device controlling the unit? If question 2 is answered as “Yes”: - Controller type (LCDM) = “Unit”...
  • Seite 135 UNIT CONTROLLER Question Description Answers Action Water calculation mode for circuit 1 heating (C1WC) = “Gradient” Underfloor heating Gradient curve for circuit 1 (C1OTC) = “0.4” Water calculation mode for circuit 1 heating (C1WC) = “Fix” Question 5a Which are the emitters of circuit 1? Fan coils Fixed T for circuit 1 (C1TF) = “45”...
  • Seite 136: Examples Of Possible Configurations

    UNIT CONTROLLER 8.5.1.4 Examples of possible configurations N O T E • Other installation configurations are possible. These are examples only for illustration purposes. • It is recommended to set firstly the Master device so as the ease the configuration of the slave devices. ...
  • Seite 137 UNIT CONTROLLER  Example 2 1- No unit controller in the unit 2- Master unit controller moved to living room Zone 1 3- Slave Unit controller as a room thermostat for Zone 2, as accessory Bedrrom Zone 2 Indoor unit Living room Zone 1 Outdoor unit Order...
  • Seite 138 UNIT CONTROLLER  Example 3 1- Master unit controller as unit configuration 2- Wired unit controller as a Room Thermostat for Zone 1 3- Wired room sensor for Zone 2 Bedrrom Zone 2 Indoor unit Living room Zone 1 Outdoor unit Order FIRST Master...
  • Seite 139 UNIT CONTROLLER  Example 4 1- Master unit controller as unit configuration 2- Wired room sensor for Zone 1 3- Wired room sensor for Zone 2 Bedrrom Zone 2 Indoor unit Living room Zone 1 Order FIRST Master Type Unit + Circuits Questions Answers Is this device attached to the unit?
  • Seite 140 UNIT CONTROLLER  Example 5 1- Master unit controller as unit configuration 2- Wireless intelligent thermostat for zone 1 (ATW-RTU-04) (Receiver + Room thermostat) 3- Wireless intelligent thermostat for zone 2 (ATW-RTU-06) (Only Room thermostat) Bedrrom Zone 2 Indoor unit Living room Zone 1 Order FIRST...
  • Seite 141: Not Allowed Configurations

    UNIT CONTROLLER 8.5.1.5 Not allowed configurations Mixed configurations (Wireless + Wired) are not allowed for YUTAKI systems. Mix Wireless + Wired Mix Wireless + Wired sensor 8.5.2 Advanced Configuration In case of executing the Advanced Configuration, the following screens are displayed. 8.5.2.1 Screen 1 Application CODE...
  • Seite 142: Screen 3

    UNIT CONTROLLER Application CODE Description Default Value Range Steps Units Notes SC S80 M If LCDM (Controller type (LCDM)) is Space Heating selected "Room" or "Unit+Room" Disabled / Swimming Pool Disabled ○ ○ ○ ○ Enabled HP Only HP + Heater “HP+Heat+Boil”...
  • Seite 143: Menu Navigation

    UNIT CONTROLLER 8.6 MENU NAVIGATION N O T E This chapter explains navigation through the menus of the controller. For more specific information about particular options in these menus, refer to the chapters Control system Optional functions at the Service Manual. In order to access to the main menu, press “...
  • Seite 144: General

    UNIT CONTROLLER The next list shows the parameters that can be consulted on the display. All of them are read-only. Most of these variables are the same ones that can be consulted by 7-segment, taking information from the outdoor and indoor unit. N O T E All the operation parameters are able to be displayed by the installer but normal user can only display the basic ones.
  • Seite 145: Circuit 2

    UNIT CONTROLLER 8.6.1.3 Circuit 2 Default Access Description Range Steps Units Application Value Notes Circuit 2 SC S80 M C2Op Operation Demand ON/OFF ○ ○ ○ ○ C2Mo Mode Comfort/ECO ○ ○ ○ ○ C2Rt Room Temp ºC ○ ○ ○...
  • Seite 146: Electrical Heater

    UNIT CONTROLLER Default Access Description Range Steps Units Application Value Notes Heat Pump SC S80 M HPTI Liquid T (R410A) ºC ○ ○ ○ ○ HPTd Discharge Gas T (R410A) ºC ○ ○ ○ ○ HPTd2 Discharge Gas T (R134a) ºC ○...
  • Seite 147: Solar Combination

    UNIT CONTROLLER 8.6.1.9 Solar Combination Available if Solar combination (SOLStSet)= “Input demand” or “Total” In the “Complementary Heating” option of the “System Configuration” menu. Default Access Description Range Steps Units Application Value Notes Solar Combination SC S80 M SOLOp Operation Demand ON/OFF ○...
  • Seite 148: System Configuration

    UNIT CONTROLLER  Capacity The following parameters can be displayed by each month selecting the specified month or for all the months selecting “Total”. Default Access Description Range Steps Units Application Value Notes Capacity SC S80 M CpSH Space Heating ○...
  • Seite 149: Holiday Mode

    UNIT CONTROLLER  Holiday Mode Default Access Description Range Steps Units Application Value Notes Holiday Mode SC S80 M absentYear Year 2015 ○ ○ ○ ○ absentMonth Month 1-12 Months ○ ○ ○ ○ absentDay 1-31 Days ○ ○ ○ ○...
  • Seite 150 UNIT CONTROLLER Default Access Description Range Steps Units Application Value Notes Room Thermostats SC S80 M None RTType Thermostats Type None Wired ○ ○ ○ ○ Wireless Compensation factors 1-12 ○ ○ ○ ○ Room Temperature Demand OFF ○ ○ ○...
  • Seite 151 UNIT CONTROLLER Circuit 2 Default Access Description Range Steps Units Application Value Notes Circuit 2 SC S80 M Rfacth1 Compen.Factor Heat OFF / 1~5 ○ ○ ○ ○ (*1) Maxfacthp1 Max Compen.Factor Heat + 0-10 ºC ○ ○ ○ ○ (*1) Maxfacthn1 Max Compen.Factor Heat -...
  • Seite 152: Timer And Schedule

    UNIT CONTROLLER Circuit 2 Default Access Description Range Steps Units Application Value Notes Circuit 2 SC S80 M RoffhC2 Room Demand OFF Heat OFF/1~5 ºC ○ ○ ○ ○ (*1) RoffcC2 Room Demand OFF Cool OFF/1~5 ºC ○ ○ ○ ○...
  • Seite 153 UNIT CONTROLLER  Circuit 2 Default Access Description Range Steps Units Application Value Notes Circuit 2 SC S80 M Heating (Air) ○ ○ ○ ○ (*1) Cooling (Air) ○ ○ ○ (*2) Heating (Water) ○ ○ ○ ○ (*3) Cooling (Water) ○...
  • Seite 154: Water Settings

    UNIT CONTROLLER • (*3): If time type= “Schedule” and if the selected timer is “Circuit 2” (Air/Water) and if exist 2 circuits in the same controller and the timer mode is the same between them. • (*4): If timer type= “Simple”. •...
  • Seite 155: Space Cooling

    UNIT CONTROLLER Circuit 1 and circuit 2 Default Access Description Range Steps Units Application Value Notes Circuit 1 and Circuit 2 SC S80 roomC1FT Fixed T. (Circuit 1) (C1Tmin) ~ (C1Tmax) ºC ○ ○ ○ ○ (*1) roomC1Grad Curve (Circuit 1) 0.2~2.2 ○...
  • Seite 156: Space Heating

    UNIT CONTROLLER 8.6.2.4 Space Heating If Controller type (LCDM)= “Unit” or “Unit+Room”. • Circuit 1 • Circuit 2  Circuit 1 and Circuit 2 • Water Calculation Mode • Eco offset • Working Limits • Mixing Valve Default Access Description Range Steps Units...
  • Seite 157 UNIT CONTROLLER Water Calculation Mode The main parameter for configuration of space heating is the water calculation temperature. The water calculation mode establishes the temperature setting for each circuit, selecting a function to assign each temperature setting depending on the ambient temperature. Each circuit has its own Water Calculation type for heating.
  • Seite 158 UNIT CONTROLLER This calculation mode sets the circuit’s temperature setting to a defined value, forcing the unit to maintain it. Variables used in these views are displayed in the following table. Default Access Description Range Steps Units Application Value Notes Points S SC S80 C1TA1L...
  • Seite 159: Space Cooling

    UNIT CONTROLLER SandSC CODE Units 2-3HP REST REST 70 (**) ºC ºC 70 (**) ºC 80 (**) ºC 55(*) 60(*) 80 (**) 55 (*) 60 (*) ºC - (*) In case of Boiler combination complementary heating activation (Heating source (HES) = Boiler or Boiler + Heater) maximum supply temperature range can be setting up to 80ºC: - (**): If R134a compressor disabled (DSW4#1: ON) setting must be 60ºC.
  • Seite 160 UNIT CONTROLLER Water Calculation Mode The main parameter for configuration of space cooling is the water calculation temperature. The water calculation establishes the temperature setting for each circuit, selecting a function to assign each temperature setting depending on the ambient temperature. Each circuit has its own Water Calculation Mode for cooling.
  • Seite 161: Working Limits

    UNIT CONTROLLER Variables used in these views are displayed in the following table. Default Access Description Range Steps Units Application Value Notes Points SC S80 M C1TA1L Low ambient T (Circuit 1) 17~30 ºC ○ ○ ○ C1TA1H High ambient T (Circuit 1) 31~45 ºC ○...
  • Seite 162: Dhw

    UNIT CONTROLLER 8.6.2.6 DHW Available if Controller type (LCDM)= “Unit” or “Unit + Room”. • Status • Mode • Control • Setting Temperature • Maximum Setting T • Differential T • HP OFF Differential T • HP ON Differential T •...
  • Seite 163 UNIT CONTROLLER  DHW Anti Legionella • Status • Operation Day • Starting Time • Setting Temperature • Duration Default Access Description Range Steps Units Application Value Notes Anti Legionella SC S80 M Disabled / DesFun Status Disabled ○ ○ ○...
  • Seite 164: Swimming Pool

    UNIT CONTROLLER 8.6.2.7 Swimming Pool Available if Controller type (LCDM)= “Unit” or “Unit + Room”. • Status • Setting Temperature • Offset Temperature Default Access Description Range Steps Units Application Value Notes Swimming Pool SC S80 M Disabled / Status Disabled ○...
  • Seite 165: Heating Source

    UNIT CONTROLLER  Heating Source Default Access Description Range Steps Units Application Value Notes Heating Source SC S80 M HP Only HP + Heater Heating source HP Only ○ ○ ○ ○ (*1) HP + Boiler HP + Heat. + Boil. N O T E (*1): “HP+Heat+Boil”...
  • Seite 166: Total Control

    UNIT CONTROLLER  Solar Combination Default Access Description Range Steps Units Application Value Notes Solar combination Disabled SOLStSet Status Disabled Input demand ○ ○ ○ ○ (*1) Total control N O T E (*1): Forced to disabled if Status (DHWs)= “Disabled”. Input demand Default Access...
  • Seite 167: Heat Pump

    UNIT CONTROLLER 8.6.2.9 Heat Pump Available if Controller type (LCDM)= “Unit” or “Unit + Room”. • Water Pump Configuration • Outdoor average Timer • Minimum ON Time • Minimum OFF Time • Emergency Operation • Seizure Protection Default Access Description Range Steps Units Application...
  • Seite 168: Optional Functions

    UNIT CONTROLLER 8.6.2.10 Optional Functions Available if Controller type (LCDM)= “Unit” or “Unit + Room”. • System • Space functions • DHW (*1) N O T E (*1) Available if Status (DHWs)= “Enabled”.  System • Hydraulic Sep. Status • Energy Configuration •...
  • Seite 169: Smart Function

    UNIT CONTROLLER Smart Function Default Access Description Range Steps Units Application Value Notes Smart Function SC S80 M TarSt Status Disabled Disabled / Enabled ○ ○ ○ ○ (0) HP Block (1) HP Limited (A) TarAct Smart Action HP blocked (2) SM Grid Ready ○...
  • Seite 170: I/O And Sensor

    UNIT CONTROLLER Auto Heat / Cool Default Access Description Range Steps Units Application Value Notes Auto Heat / Cool Status Disable Disabled /Enabled ○ ○ ○ (*1) Hoff Switch to Heat T 10~23 ºC ○ ○ ○ (*2) Coff Switch to Cool T 24~35 ºC ○...
  • Seite 171 UNIT CONTROLLER Inputs range visualizations and constraints table: Available at Constraints Value Visibility Disabled Always Available if some of the Water Calculation modes (Water calculation mode for circuit 1 heating (C1WC) or Water calculation mode for circuit 1 cooling Demand On/Off (CC1WC) or Water calculation mode for circuit 2 heating (C2WC) or Water calculation mode for circuit 2 cooling (CC2WC)) are not set as “Disabled”.
  • Seite 172 UNIT CONTROLLER  Outputs Access Description Default Value Range Steps Units Application Notes Outputs SC S80 M SWP 3WV Output 1 ○ ○ ○ ○ (if SWP) Water Pump3 Output 2 ○ ○ ○ ○ (if boiler or hydraulic separator) Boiler (if boiler) / Relay 1 Output 3 ○...
  • Seite 173: Controller Settings

    UNIT CONTROLLER  Auxiliary Sensors Access Description Default Value Range Steps Units Application Notes Auxiliary Sensors SC S80 M Taux1 Sensor 1 Two3 (if Boiler) ○ ○ ○ ○ *See “Inputs range Taux2 Sensor 2 Swimming pool (if SWP existing) visualization and ○...
  • Seite 174: Controller Options

    UNIT CONTROLLER 8.6.3.1 Controller Options Default Access Description Range Steps Units Application Value Notes Controller Options SC S80 M Unit LCDUop Operation view Unit (*4) ○ ○ ○ ○ (*1) Room Holiday Eco / Comfort ButtonAction Favourite Action ○ ○ ○...
  • Seite 175 UNIT CONTROLLER Default Access Description Range Steps Units Application Value Notes Date and Time SC S80 Adjust Date and Time ○ ○ ○ ○ euSumerTime European Summer Time Disabled Enabled / Disabled ○ ○ ○ ○ UTC Zone 0 to 12 ○...
  • Seite 176: Screen Settings

    UNIT CONTROLLER  UTC Zone When European Summer time is selected as “Enabled”. Europe spans 7 primary time zones (5 of them can be seen on the map in this article, while 2 other zones contain the European part of Kazakhstan and some very eastern territories of European Russia). Most of European countries use daylight saving time and switch to it at the same moment, which is ‘harmonise’...
  • Seite 177: Commisioning

    UNIT CONTROLLER 8.6.4 Commisioning • Air Purge Procedure • Unit Test Run • Screed Drying Default Access Description Range Steps Units Application Value Notes Unit Test Run Air purge procedure ○ ○ ○ ○ Unit test run ○ ○ ○ ○...
  • Seite 178: Screed Drying

    UNIT CONTROLLER 8.6.4.3 Screed Drying Default Access Description Range Steps Units Application Value Notes Screed Drying SDC1 Circuit 1 Setting T Limits installer ºC ○ ○ ○ ○ (*1) SDC2 Circuit 2 Setting T Limits installer ºC ○ ○ ○ ○...
  • Seite 179: Factory Reset

    UNIT CONTROLLER 8.6.6 Factory Reset This function is only visible for the installer. It asks for removing all the settings and retourns to the factory setting configuration. 8.6.7 Return to user mode This function allows to getting out of the “Installer mode”. PMML0335A rev.1 - 04/2016...
  • Seite 180: Index Of References

    UNIT CONTROLLER 8.7 INDEX OF REFERENCES REFERENCE PAGE absentDay ..................137 C2Op ...................133 absentMonth ...................137 C2OTC ...................146 absentSetting..................137 C2OTCs ..................133 absentTime ..................137 C2OTO ...................146 absentYear ..................137 C2OTO ...................149 ...................158 C2PBMV ..................146 AutoDiff ...................157 C2PBMV ..................149 AutoDiff ...................158 C2RS ...................133 AutoST ...................157 C2Rt ...................133 AutoST ...................158...
  • Seite 181 UNIT CONTROLLER DHWOp ..................133 ...................158 DHWr ...................150 IpDHW ...................135 DHWs ...................129 IpSC ...................135 DHWs ...................150 IpSH ...................135 DHWSHst ..................133 IpSWP ...................135 DHW-SMART .................157 IpTot ...................135 DHWst ...................133 KeepP ...................151 DHWt ...................133 ...................157 EHLF ...................134 LCDBrightness ................164 EHOp ...................134 LCDContrast ...................164 EHst ...................134 LCDL...
  • Seite 182 UNIT CONTROLLER Rton ...................155 Taux1 ...................161 Rton ...................155 Taux2 ...................127 RTType ...................130 Taux2 ...................161 RTType ...................138 Taux3 ...................127 SDC1 ...................166 Taux3 ...................161 SDC2 ...................166 TDHWmax ..................150 SHPT ...................150 TDHWMAXtime ................150 SHPTs ...................150 TDHWON ..................150 SHWTS ...................151 TDHWS ..................150 SOLAnz ..................154 TDHWTMAX ...................154 Solarmin ..................154 tempOffset ..................162...
  • Seite 183: Troubleshooting

    TROUBLESHOOTING 9 TROUBLESHOOTING Alarm code indication on remote control switch: Alarm indication Alarm code  Alarms for Indoor units: Retry Alarm Yutaki Yutaki Yutaki Stop Origin Detail of Abnormality Main Factors Code S/SC Code Transmission Alarm (Not outdoor Loose, disconnected, broken or Communication unit detected) short-circuited connector...
  • Seite 184 TROUBLESHOOTING Retry Alarm Yutaki Yutaki Yutaki Stop Origin Detail of Abnormality Main Factors Code S/SC Code Freeze Protection by Cold water Indoor inlet, outlet temperature detection Freeze Protection Stop by indoor Indoor liquid temperature thermistor No Opentherm/Hlink Indoor-LCD Receiver Communication failure communication for a continuous period of 10 minutes.
  • Seite 185 TROUBLESHOOTING  Alarms for Outdoor units Code Category Type of abnormality Main cause number Activation of PSH, locked motor, abnormal operation in the power supply phase. Activation of protection device (high pressure Failure of fan motor, drain discharge, PCB, relay, float switch Outdoor unit cut) activated.
  • Seite 186: Maintenance

    MAINTENANCE Code Category Type of abnormality Main cause number Incorrect setting address or refrigerant cycle Over 64 indoor units setting by number or indoor unit address. Number setting Incorrect setting of indoor unit number for The number of indoor units connected to the H-LINK II of one H-LINK type system is 17 or higher.
  • Seite 187: General Maintenance Procedure For The Indoor Unit

    MAINTENANCE contact that is caused by the loosened terminal connections, the oxidized contacts, the foreign matter and other items. Check the electrical insulation resistance. 6 Control device and protection device • Setting: Do not readjust the setting in the field unless the setting is maintained at a point that is different from the point listed in the Technical Documentation.
  • Seite 188 MAINTENANCE The manometer is placed at different positions according to each unit model Yutaki S / SCombi In Yutaki S and SCombi models, the manometer is installed factory supplied as it is shown: Yutaki S Yutaki S Combi Manometer Manometer Yutaki M For the Yutaki M series it is highly recommended to install, field supplied, a manometer gauge attached to the water inlet pipe and after the shut-off valve.
  • Seite 189 MAINTENANCE 5 DHWTank inspection hatch The DHW tank has an inspection hatch at the bottom. This hatch allows the inspection of the interior of the tank. D A N G E R Be careful when using this inspection hatch. There are high temperature and high pressure inside the tank. Before open it wait a reasonable time for the water to cool.
  • Seite 190: Safety Valve

    MAINTENANCE 7 Safety valve • Operation: Check the correct operation of the indoor unit safety valve (pressure relief valve) on the space heating circuit. Open it manually and some water should be expelled by its connected drain pipe. 8 Air purger: •...
  • Seite 191 MAINTENANCE  Draining N O T E Draining operation is unique for each model. Refer to the service manual of the specific unit for drain operation procedure. Draining operation for YUTAKI S YUTAKI S models have no drain port factory supplied. It must be considered the installation of a drain port after the shut-off valve (factory supplied) and before the water inlet of the unit when proceding to the installation of the unit.
  • Seite 192 MAINTENANCE Draining operation for YUTAKI M YUTAKI M has no drain port factory supplied. It is highly recommended to install a drain port valve attached to the water outlet of the YUTAKI M unit in order to ease the operation of draining. When the drain port is installed the draining procedure for the YUTAKI M follows the next steps: 1 Switch OFF the main power of the unit.
  • Seite 194: Printed In Spain

    Hitachi Air Conditioning Products Europe, SAU Ronda Shimizu, 1 - Políg. Ind. Can Torrella 08233 Vacarisses (Barcelona) Spain © Copyright 2016 HITACHI Air Conditioning Products Europe, S.A.U. – All rights reserved. Printed in Spain...