40
| Configuration
Switch between 12 and 24 hours time format.
• Contact information: contractor, installer, service, phone, website, e-mail, etc.
• Display settings: screen brightness and screen behavior in standby mode.
7.7.6

Service

All unit parameters and settings can be changed in the Service menu.
The Service menu is locked by default and it is necessary to enter a password (default
password is 1111).
7.7.6.1 Input
Configuration of inputs
Settings for analog, digital and universal input terminals on the main board and connection board, configuration of
functionality.
Table 2 Digital universal inputs available for selection
User modes
Central Vacuum Cleaner
Cooker hood function
External Stop
Extra controller Alarm
Change-over feedback
Fire Alarm
Configurable Digital
Input 1
Configurable Digital
Input 2
Configurable Digital
Input 3
Pressure Guard
Relative humidity and rotation speed signals from fans are already pre-addressed to specific terminals and cannot be
changed, all other inputs are free for configuration by commissioning. Inputs are free to be used for any purpose.
Universal input (UI) configured as universal analog input (UAI) can be configured for several inputs because multiple
sensors of the same type can be used. Universal analog inputs (UAI) have only selections for RH Sensor (RH), CO₂
Sensor (CO₂), Supply Air Fan Control (SAFC) and Extract Air Fan Control (EAFC) wired configurations.
Analog input (AI) temperature sensors are not allowed to be configured more than once.
Same user modes can be configured on multiple digital inputs (for example multiple bathrooms can be connected to dif-
ferent digital inputs with Refresh mode configured for each.
Digital inputs can be configured to be normally open (Normally Open (NO)) or normally closed (Normally Closed
(NC)). Default setting is Normally Open (NO). Not available for wireless inputs.
A time delay for user modes activated via digital input can be switched off or enabled. Time delay indicates how long
the user mode remains active after its duration of operation has expired.
PDM (pulse density modulation) input for relative humidity (RH) sensor on the main board is pre-adressed and cannot
be changed.
Activation of specific user modes.
Activation of Central vacuum cleaner function.
Activation of Cooker Hood function.
Air handling unit is stopped by an external command.
Indication about an alarm in external controller. Used for Extra Heater/Cooler/
Preheater.
Used with Change-over systems. Indicate if the temperature of heating/cooling fluid
in the system is right.
Air handling unit is stopped due to fire. Can be used with smoke alarms or similar.
Activation of custom airflows set by user.
Activation of custom airflows set by user.
Activation of custom airflows set by user.
Digital input from a pressure guard component
GB
212193 | v04