7.9

UL-gerechte Installation

HINWEIS
Folgendes Kapitel wird unabhängig von der Sprache dieser Dokumentation aufgrund
von UL-Anforderungen immer in englischer Sprache abgedruckt.
HINWEIS
Der UL-Aufkleber ist am Gerät oder in unmittelbarer Nähe zum Gerät anzubringen.
7.9.1

Field wiring power terminals

X4
7.9.2

Short circuit current rating

Suitable for use on a circuit capable of delivering not more than
7.9.3

Branch circuit protection

Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
AC 380 V – 480 V / 500 V devices
Non semiconductor fuses (currents
Non-Semiconductor fuses Class CA, CB, CC, CD, CF, G, J, K-1, K-5, RK1, RK5, T,
can be used.
Use 75 °C copper wire only.
Tighten terminals to in-lbs (Nm) as follows:
Supply connection
Spring terminal
Wire sizes 19 – 10 AWG
65,000 rms symmetrical amperes when protected by fuses, circuit breakers as de-
scribed in the tables below.
If you use cable cross sections that are dimensioned for a smaller current than the
rated current of the unit, make sure that the fuse is dimensioned for the used cable
cross section.
For information on selecting cable cross sections, refer to the project planning ma-
nual.
Comply with the country-specific installation regulations in addition to the above
notes.
are maximum values)
Max 100 A / 500 V
Betriebsanleitung – Sicheres Bremsmodul SBM für Schaltschrank-Einbau
Tightening torque in-lbs (Nm)
X14
PE connection
M4: 12.39 – 14.16 (1.4 – 1.6)
SCCR: 65 kA / 500 V
Inverse-time circuit breaker (currents
are maximum values)
Max 100 A / 500 V min.
Elektrische Installation
UL-gerechte Installation
Brake terminal
Spring terminal
Wire sizes 19 – 14 AWG
Type E Combination Motor
Controller
Siemens
3RV2041-4YA10
max. 93 A
7
55