Mechanische Installation
4
UL-gerechte Installation
4.2
UL-gerechte Installation
4.2.1
UL- und cUL-Installation
Validity
Suitability
Expansion units
Battery
Flat surface
Power terminals
22
Betriebsanleitung – WOP11D-70-0, WOP11D-100-0 und WOP11D-150-0
HINWEIS
Das folgende Kapitel wird unabhängig von der Sprache dieser Dokumentation auf-
grund von UL-Anforderungen immer in englischer Sprache abgedruckt.
This section is only valid for UL labeled panels.
•
This equipment is suitable for use in Class 2 non-hazardous locations only.
•
Combinations of equipment in your system are subject to investigation by the local
authority having jurisdiction at the time of installation.
•
All devices have to be supplied by a Class 2 power supply.
Only UL and cUL approved expansion units are allowed to be connected to the port
designated "EXPANSION". At the moment there are no such units evaluated or allo-
wed.
Battery may explode if mistreated. Do not recharge, disassemble or dispose of in fire.
•
This product contains a battery; this must only be changed in an area known to be
non-hazardous.
•
Replace the battery with a BR 2032 battery. Use of another type of battery may
present a risk of fire or explosion.
For use on a flat surface of a type 4X enclosure indoor use only.
Use minimum 75 °C copper wire only.