Herunterladen Inhalt Inhalt Diese Seite drucken

Marking And Description Of Temperature Sensors; Sensor Simulation - flamco MeiTronic W10B Bedienungsanleitung

Witterungsgeführte heizungsregler
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BASIC DESCRIPTIONS OF
EN
CONTROLLER OPERATION
MARKING AND DESCRIPTION OF TEMPERATURE
SENSORS
Temperature sensors, which contain Pt1000 sensor elements, are marked with »XX/Pt«.
TABLE: resistance of Pt1000 temperature sensors
Temperature
Resistance
[°C]
[Ω]
-20
922
-15
941
-10
961
-5
980
0
1000
5
1020
10
1039
15
1058
20
1078
25
1097
30
1117

SENSOR SIMULATION

The W.. controller has a special function installed, which enables simulations of all sen-
sors. With the help of this function, users can test controller operation.
This function is intended for the case of start-up, maintenance or testing of a
controller. Sensor simulation is activated by selecting the screen with hydraulic scheme
display with the
The controller will switch over to the simulation operation mode.
Move between sensors by pressing the
With buttons
The simulated sensor mark will change from T to S.
Simulation operation mode is deactivated by pressing the
if no button is pressed for more than 5 minutes.
84
Temperature
Resistance
[°C]
[Ω]
35
1136
40
1155
45
1175
50
1194
55
1213
60
1232
65
1252
70
1271
75
1290
80
1309
85
1328
button. Press the
and
set the temperature value for each selected sensor.
Temperature
Resistance
[°C]
[Ω]
90
1347
95
1366
100
1385
105
1404
110
1423
115
1442
120
1461
125
1480
130
1498
135
1515
140
1536
button and hold it for 10 seconds.
button.
button for 10 seconds or
Temperature
Resistance
[°C]
[Ω]
145
1555
150
1573
155
1592
160
1611
165
1629
170
1648
175
1666
180
1685
185
1703
190
1722
195
1740
Service setting manual

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Meitronic w10Meitronic w20

Inhaltsverzeichnis